DCS trunk cable MTP, 12-144 fibres OS2
for interconnecting DCS modules
This product is not available in your region!
DCS trunk cable MTP, 12-144 fibres OS2
Product variants & stock
Article No. | Stock | Product | Outer sheath colour | Number of fibres | Outer sheath diameter [mm] | Minimum bending radius | Tensile load short term [N] | Tensile load continuous [N] | Crush resistance short term [N] | Crush resistance continuous [N] | Polarity | Number of connectors side A | Number of connectors side B | Number of fibres per connector A | Number of fibres per connector B | Weight [kg] | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
474040 | DCS trunk cable 1x MTP - 1x MTP | yellow | 12 | 5.9 | 120 | 3000 | 1000 | 4000 | 1200 | A | 1 | 1 | 12 | 12 | 0.3 kg | by the metre | 40393910144161 | |
474041 | DCS trunk cable 2x MTP - 2x MTP | yellow | 24 | 9.9 | 200 | 8000 | 4100 | 4000 | 1200 | A | 2 | 2 | 12 | 12 | 0.3 kg | by the metre | 40393910144154 | |
474042 | DCS trunk cable 4x MTP - 4x MTP | yellow | 48 | 9.9 | 200 | 8000 | 4100 | 4000 | 1200 | A | 4 | 4 | 12 | 12 | 0.3 kg | by the metre | 40393910144147 | |
474043 | DCS trunk cable 6x MTP - 6x MTP | yellow | 72 | 10.7 | 215 | 8000 | 4100 | 4000 | 1200 | A | 6 | 6 | 12 | 12 | 0.3 kg | by the metre | 40393910144130 | |
474044 | DCS trunk cable 8x MTP - 8x MTP | yellow | 96 | 12.9 | 255 | 8000 | 4100 | 4000 | 1200 | A | 8 | 8 | 12 | 12 | 0.3 kg | by the metre | 40393910144123 | |
474045 | DCS trunk cable 12x MTP - 12x MTP | yellow | 144 | 15.8 | 320 | 8000 | 4100 | 4000 | 1200 | A | 12 | 12 | 12 | 12 | 0.3 kg | by the metre | 40393910144116 | |
474050 | DCS trunk cable 1x MTP - 1x MTP | yellow | 12 | 5.9 | 120 | 3000 | 1000 | 4000 | 1200 | C | 1 | 1 | 12 | 12 | 0.3 kg | by the metre | 40393910144109 | |
474051 | DCS trunk cable 2x MTP - 2x MTP | yellow | 24 | 9.9 | 200 | 8000 | 4100 | 4000 | 1200 | C | 2 | 2 | 12 | 12 | 0.3 kg | by the metre | 40393910144093 | |
474052 | DCS trunk cable 4x MTP - 4x MTP | yellow | 48 | 9.9 | 200 | 8000 | 4100 | 4000 | 1200 | C | 4 | 4 | 12 | 12 | 0.3 kg | by the metre | 40393910144086 | |
474053 | DCS trunk cable 6x MTP - 6x MTP | yellow | 72 | 10.7 | 215 | 8000 | 4100 | 4000 | 1200 | C | 6 | 6 | 12 | 12 | 0.3 kg | by the metre | 40393910144079 | |
474054 | DCS trunk cable 8x MTP - 8x MTP | yellow | 96 | 12.9 | 255 | 8000 | 4100 | 4000 | 1200 | C | 8 | 8 | 12 | 12 | 0.3 kg | by the metre | 40393910144062 | |
474055 | DCS trunk cable 12x MTP - 12x MTP | yellow | 144 | 15.8 | 320 | 8000 | 4100 | 4000 | 1200 | C | 12 | 12 | 12 | 12 | 0.3 kg | by the metre | 40393910144055 |
Technical specifications
Compact, metal-free cable construction with FR/LS0H cable sheath and 12 to 144 fibres.
OS2 versions with Euroclass D<sub>ca</sub> are available (Euroclass C<sub>ca</sub> or B2<sub>ca</sub> version available on request).
Sticker labelling at both cable ends.
The length of individual cables ("legs") may be defined on the basis of a specific project (standard 0.75 m).
The leg separation is effected with a divider housing.
All individual cables are assembled using MTP<sup>®</sup> connectors with high-performance 12-fibre Elite<sup>®</sup> ferrules (MTP<sub>8</sub>/MTP<sub>24</sub> available on request).
Standard connectivity methods can be type A or type C (other types available on request).
The cables are fitted at both ends with protective sleeves.
DCS trunk cable (FR/LS0H) with 12-144 fibres OS2. High-performance connector assembly at either end with MTP Elite (male). Sticker labelling at both cable ends. |
OS2 MTP-on-MTP trunk cables are suitable for all high-performance applications with duplex and parallel optic signals in a data centre environment. They are particularly used when installation requires sturdy, metal-free indoor cables that provide enhanced crush resistance and rodent protection. For duplex applications, the pre-assempled connectors at either end of the cable are connected to the DCS modules. The DCS trunk cables are assembled to a very high quality and guarantee optimum values for optical performance (IL/RL). |
Housing colour connector A | yellow |
---|---|
Housing colour connector B | yellow |
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2 |
---|---|
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2 |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 |
Flame spread | IEC 60332-3-24 |
MTP standard (IEC) | IEC 61754-7, IEC 61755-3-31, IEC 61755-3-32 |
Polarity standard | TIA-568-C.3 Type A,B,C |
Outer sheath material | FR/LSZH |
---|---|
Outer sheath colour | yellow |
Fibre type | E9/125 G.652.D BLO |
---|---|
Colour code | IEC 60304 |
Connector type side A | MTP |
Connector gender side A | male |
Ferrule polishing connector A | Elite APC 8° |
IL maximal, connector A | 0.3 dB |
IL typical, connector A | 0.1 dB |
RL minimal, connector A | 65 dB |
RL typical, connector A | 70 dB |
Connector type side B | MTP |
Connector gender side B | male |
Ferrule polishing connector B | Elite APC 8° |
IL maximal, connector B | 0.3 dB |
IL typical, connector B | 0.1 dB |
RL minimal, connector B | 65 dB |
RL typical, connector B | 70 dB |