DCS breakout cable, MTP - MTP, E9/125 G.652.D BLO
for interconnecting DCS modules
DCS breakout cable MTP, 12-144 fibres OS2
Product variants & stock
Article No. | Stock | Product | Number of fibres | Outer sheath diameter [mm] | Tube diameter [mm] | Polarity | Number of connectors side A | Number of connectors side B | Gradation | Weight [kg] | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|
475040 | DCS breakout cable 1x MTP - 1x MTP | 12 | 4.5 | 2.0 | A | 1 | 1 | 0.3 kg | by the metre | 40393910143553 | ||
475041 | DCS breakout cable 2x MTP - 2x MTP | 24 | 6.6 | 2.0 | A | 2 | 2 | equal length | 0.3 kg | by the metre | 40393910143546 | |
475042 | DCS breakout cable 4x MTP - 4x MTP | 48 | 6.6 | 2.0 | A | 4 | 4 | equal length | 0.3 kg | by the metre | 40393910143539 | |
475043 | DCS breakout cable 6x MTP - 6x MTP | 72 | 7.8 | 2.0 | A | 6 | 6 | graduated length | 0.3 kg | by the metre | 40393910143522 | |
475044 | DCS breakout cable 8x MTP - 8x MTP | 96 | 9.2 | 2.0 | A | 8 | 8 | graduated length | 0.3 kg | by the metre | 40393910143515 | |
475045 | DCS breakout cable 12x MTP - 12x MTP | 144 | 12.5 | 2.0 | A | 12 | 12 | graduated length | 0.3 kg | by the metre | 40393910143508 | |
475050 | DCS breakout cable 1x MTP - 1x MTP | 12 | 4.5 | 2.0 | C | 1 | 1 | 0.3 kg | by the metre | 40393910143492 | ||
475051 | DCS breakout cable 2x MTP - 2x MTP | 24 | 6.6 | 2.0 | C | 2 | 2 | equal length | 0.3 kg | by the metre | 40393910143485 | |
475052 | DCS breakout cable 4x MTP - 4x MTP | 48 | 6.6 | 2.0 | C | 4 | 4 | equal length | 0.3 kg | by the metre | 40393910143478 | |
475053 | DCS breakout cable 6x MTP - 6x MTP | 72 | 7.8 | 2.0 | C | 6 | 6 | graduated length | 0.3 kg | by the metre | 40393910143461 | |
475054 | DCS breakout cable 8x MTP - 8x MTP | 96 | 9.2 | 2.0 | C | 8 | 8 | graduated length | 0.3 kg | by the metre | 40393910143454 | |
475055 | DCS breakout cable 12x MTP - 12x MTP | 144 | 12.5 | 2.0 | C | 12 | 12 | graduated length | 0.3 kg | by the metre | 40393910143447 |
Technical specifications
Compact, metal-free cable construction with FR/LS0H cable sheath and 12 to 144 fibres.
Sticker labelling at both cable ends.
The length of individual cables ("legs") may be defined on the basis of a specific project (standard 0.75 m).
All individual cables are assembled using MTP® connectors with high-performance 12-fibre Elite® ferrules (MTP8/MTP24 available on request).
Standard connectivity methods can be type A or type C (other types available on request).
The cables are fitted at both ends with protective sleeves.
Sticker labelling at both cable ends.
The length of individual cables ("legs") may be defined on the basis of a specific project (standard 0.75 m).
All individual cables are assembled using MTP® connectors with high-performance 12-fibre Elite® ferrules (MTP8/MTP24 available on request).
Standard connectivity methods can be type A or type C (other types available on request).
The cables are fitted at both ends with protective sleeves.
Cable raw material | FO Indoor M-BO / J-F(ZN)HH |
---|
DCS breakout cable (FR/LS0H) with 12-144 fibres OS2. High-performance connector assembly at either end with MTP Elite (male). Sticker labelling at both cable ends. |
Housing colour connector A | yellow |
---|---|
Housing colour connector B | yellow |
MTP breakout cables are suitable for all high-performance applications with duplex and parallel optic signals in a data centre environment. They are particularly used when installation requires sturdy, metal-free indoor cables that provide enhanced crush resistance. For duplex applications, the pre-assempled connectors at either end of the cable are connected to the DCS modules. The DCS breakout cables are assembled to a very high quality and guarantee optimum values for optical performance (IL/RL). |
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2 |
---|---|
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2 |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 |
Flame spread | IEC 60332-3-24 |
MTP standard (IEC) | IEC 61754-7, IEC 61755-3-31, IEC 61755-3-32 |
Polarity standard | TIA-568-C.3 Type A,B,C |
Outer sheath material | FR/LSZH |
---|---|
Outer sheath colour | yellow |
Fibre type | E9/125 G.652.D BLO |
---|---|
Colour code | IEC 60304 |
Connector type side A | MTP |
Connector gender side A | male |
Ferrule polishing connector A | Elite APC 8° |
IL maximal, connector A | 0.3 dB |
IL typical, connector A | 0.1 dB |
RL minimal, connector A | 65 dB |
RL typical, connector A | 70 dB |
Connector type side B | MTP |
Connector gender side B | male |
Ferrule polishing connector B | Elite APC 8° |
IL maximal, connector B | 0.3 dB |
IL typical, connector B | 0.1 dB |
RL minimal, connector B | 65 dB |
RL typical, connector B | 70 dB |