Multimode fibre, G50/125/250, OM5
                            bend optimized
                                                            
                                IEC 60793-2-10 Type A1-OM5b, ISO/IEC 11801 OM5, TIA/EIA 492AAAE
                                                    
1 Core
2 Cladding
3 Coating
Technical specifications
                                        Bend insensitive fibre with enhanced macrobending features, particularly recommended for high-performance transmissions in the 850-950 nm wavelength.
The geometrical, optical and mechanical specifications meet or exceed all relevant international standards.
                                The geometrical, optical and mechanical specifications meet or exceed all relevant international standards.
| Numerical aperture tolerance - | 0.015 | 
|---|---|
| Numerical aperture tolerance + | 0.015 | 
| Numerical Aperture | 0.200 | 
| In Premises cabling for LAN backbones (Campus and Vertical/Riser cabling) as well as in Data Centres. | 
| Fiber specifications | IEC 60793-2-10 Type A1-OM5b, ISO/IEC 11801-OM5, ITU-T G.651.1, TIA/EIA 492AAAE | 
|---|---|
| Cabling standards | ISO/IEC 11801-1, EN 50173-1 | 
| Core diameter [µm] | 50.0 +/- 2.5 | 
|---|---|
| Cladding diameter [µm] | 125.0 +/- 1.0 | 
| Coating diameter [µm] | 242 +/- 5 | 
| Maximum cladding non-circularity[%] | 1.0 % | 
| Maximum cladding/Coating concentricity error [µm] | 10 µm | 
| Maximum core non-circularity [%] | 5.0 % | 
| Maximum core/cladding concentricity error [µm] | 1.5 µm | 
| Test load [kpsi] | 100 kpsi |