FE180 E30 CL
Safety cable, 0.6/1kV, armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
1 Conductor: solid / stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH
Productvarianten & voorraad
Downloaden
Artikelnr. | Voorraad | Artikel | Aantal kernen | Diameter mm² | Buitenmanteldiameter [mm] | Cu tarief [kg/km] | Gewicht [kg/km] | Brandlast [kWh/m] | Geleider | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|
193886 | FE180 E30 CL | 3 | 1.5 | 11 | 43 | 210 | 0.46 | massief | 40393910065367 | |
187199 | FE180 E30 CL | 3 | 2.5 | 12 | 72 | 255 | 0.50 | massief | 40393910074345 | |
191097 | FE180 E30 CL | 3 | 4 | 14 | 115 | 373 | 0.69 | massief | 40393910069785 | |
191121 | FE180 E30 CL | 3 | 6 | 15.8 | 173 | 481 | 0.90 | massief | 40393910069648 | |
188354 | FE180 E30 CL | 3 | 10 | 18 | 288 | 651 | 1.20 | massief | 40393910072303 | |
191595 | FE180 E30 CL | 4 | 2.5 | 14 | 96 | 296 | 0.56 | massief | 40393910069143 | |
187167 | FE180 E30 CL | 4 | 4 | 16 | 154 | 408 | 0.79 | massief | 40393910074512 | |
188352 | FE180 E30 CL | 4 | 6 | 17 | 230 | 535 | 1.06 | massief | 40393910072327 | |
191038 | FE180 E30 CL | 5 | 2.5 | 14 | 120 | 388 | 0.76 | massief | 40393910070040 | |
188350 | FE180 E30 CL | 5 | 4 | 16 | 192 | 488 | 1.05 | massief | 40393910072341 | |
188353 | FE180 E30 CL | 5 | 6 | 17.5 | 288 | 640 | 1.28 | massief | 40393910072310 | |
188397 | FE180 E30 CL | 5 | 10 | 21 | 480 | 964 | 1.76 | massief | 40393910072082 | |
187197 | FE180 E30 CL | 7 | 2.5 | 16 | 168 | 476 | 0.91 | massief | 40393910074369 | |
188355 | FE180 E30 CL | 7 | 6 | 19 | 403 | 794 | 1.53 | massief | 40393910072297 | |
188356 | FE180 E30 CL | 7 | 10 | 23 | 672 | 1201 | 2.13 | massief | 40393910072280 | |
192461 | FE180 E30 CL | 8 | 1.5 | 15 | 115 | 403 | 0.85 | massief | 40393910067477 | |
187128 | FE180 E30 CL | 8 | 2.5 | 16 | 192 | 489 | 1.04 | massief | 40393910074642 | |
191104 | FE180 E30 CL | 8 | 4 | 18 | 308 | 684 | 1.36 | massief | 40393910069754 |
Technische specificaties
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimale buigradius permanent (multi-core) | 12 x D |
---|---|
Minimale buiging tijdens installatie (enkele kern) | 15 x D |
Minimale buigradius permanent (enkele kern) | 15 x D |
Minimale buiging tijdens installatie (multi-core) | 12 x D |
Integriteit van de isolatie | FE 180 |
---|---|
Circuit Integriteit | E30 |
Installatietemperatuur | -5 °C - +50 °C |
Bedrijfstemperatuur | -45 °C - +90 °C |
Testspanning bij 50Hz | 3500 |
---|---|
Nominal voltage | 0.6/1kV |
* System Circuit Integrity is dependent on installation method |
Geleider | Blanke koperkern, massief of samengeslagen, volgens IEC 60228 en EN 60228 (≥16 mm2: volgens VDE 0295) |
---|---|
Aderisolatie | Vernet polymeer volgensHD 604 S1 part 5 H (≥16 mm2: dubbellelaag-isolatie, vernet polymeer volgens VDE 0266 "HXI1" |
Aderkleuren | CENELEC HD 308 S2 |
Opvulling | HD 604 S1 part 5 H (≥16 mm2: speciale verbinding, vlamvertragend, halogeenvrij) |
Binnenmantel | Verbinding volgens HD 604 S1 part 5 H (≥16 mm2: verbinding volgens VDE 0276-604, CENELEC HD 604 S1 "HM 4", vlamvertragend) |
Bewapening (bescherming tegen knaagdieren) | Eenaderige kabel met koperband (CLCU) en meeraderige kabel met gegalvaniseerde staalband (CL) |
Buitenmantel | Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293) |
Isolatiebehoud | IEC 60331-11/-21 (180 Notulen), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 Notulen), IEC 60331-2 (120 Notulen), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
---|---|
Functiebehoud | DIN 4102-12, AREI-RGIE Section 4.3.3 FR2 |
Rookdichtheid | EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD, SEV TP 20B/3C 3.4.3 |
Nulhalogeen geen corrosieve gassen | EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA, SEV TPV11 |
Vlamdovend | EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1, SEV TP 20B/3C 3.4.1.1 |
Vlam verspreid | EN 60332-3-24, IEC 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Section 4.3.3 F2, SEV TP 20B/3C 3.4.1.3 |