(N)HXH FE180 E30-E60

Safety cable, 0.6/1kV, Keram
Halogen-free, with improved fire characteristics;
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock ProductDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionPacking unitGTIN / EAN
171290
(N)HXH-0 FE180 E30-E60 1 x 667.658.61120.23solidLby the metre40393910078862
171291
(N)HXH-0 FE180 E30-E60 1 x 10108.4961560.27solidLby the metre40393910078855
171370
(N)HXH-0 FE180 E30-E60 1 x 16169.81542270.34strandedLby the metre40393910078756
171377
(N)HXH-0 FE180 E30-E60 1 x 252511.32403290.43strandedLby the metre40393910078749
171386
(N)HXH-0 FE180 E30-E60 1 x 353512.43364280.48strandedLby the metre40393910078725
171394
(N)HXH-0 FE180 E30-E60 1 x 505013.94805650.58strandedLby the metre40393910078701
171429
(N)HXH-0 FE180 E30-E60 1 x 707015.76727730.68strandedLby the metre40393910078671
170842
(N)HXH-0 FE180 E30-E60 1 x 959518.191210340.91strandedLby the metre40393910079135
170845
(N)HXH-0 FE180 E30-E60 1 x 12012019.2115212700.97strandedLby the metre40393910079128
170850
(N)HXH FE180 E30-E60 1 x 15015021.4144015901.20strandedLby the metre40393910079098
170855
(N)HXH-0 FE180 E30-E60 1 x 18518523.6177619611.46strandedLby the metre40393910079074
170858
(N)HXH-0 FE180 E30-E60 1 x 24024026.8230425631.81strandedLby the metre40393910079067
170860
(N)HXH FE180 E30-E60 1x30030029.2288030912.13strandedLby the metre40393910079050
192572
(N)HXH FE180 E30-E60 2 x 1.51.511291770.48solid2Lby the metre40393910067101
186280
(N)HXH FE180 E30-E60 2 x 1.51.511291770.48solidLNby the metre40393910076134
192582
(N)HXH FE180 E30-E60 2 x 2.52.511.8482160.54solid2Lby the metre40393910067057
186921
(N)HXH FE180 E30-E60 2 x 2.52.511.8482160.54solidLNby the metre40393910075588
186922
(N)HXH FE180 E30-E60 2 x 4412.8772710.62solidLNby the metre40393910075571
186923
(N)HXH FE180 E30-E60 2 x 6613.81153350.70solidLNby the metre40393910075564
186924
(N)HXH FE180 E30-E60 2 x 101015.41924550.83solidLNby the metre40393910075557
186952
(N)HXH FE180 E30-E60 2 x 161618.23076601.09solidLNby the metre40393910075274
190404
(N)HXH FE180 E30-E60 2 x 252521.24809501.42strandedLNby the metre40393910070989
18692500ZZ
(N)HXH-J FE180 E30-E60 3 x 1.51.511.5431990.53solidLNPEby the metre40393910038088
18692500ZL
(N)HXH-J FE180 E30-E60 3 x 1.51.511.5432000.53solidLNPE500 m drum40393910038125
18692500ZK
(N)HXH-J FE180 E30-E60 3 x 1.51.511.5432000.53solidLNPE1000 m drum40393910038132
18692600ZZ
(N)HXH-J FE180 E30-E60 3 x 2.52.512.4722480.60solidLNPEby the metre40393910038026
18692600ZL
(N)HXH-J FE180 E30-E60 3 x 2.52.512.4722500.60solidLNPE500 m drum40393910038057
18692600ZK
(N)HXH-J FE180 E30-E60 3 x 2.52.512.4722500.60solidLNPE1000 m drum40393910038064
186927
(N)HXH-J FE180 E30-E60 3 x 4413.51153190.68solidLNPEby the metre40393910075526
186928
(N)HXH-J FE180 E30-E60 3 x 6614.61734000.77solidLNPEby the metre40393910075519
186929
(N)HXH-J FE180 E30-E60 3 x 101016.32885540.91solidLNPEby the metre40393910075502
186953
(N)HXH FE180 E30-E60 3 x 161619.34618091.19strandedLNPEby the metre40393910075267
186955
(N)HXH FE180 E30-E60 3 x 252522.672011821.56strandedLNPEby the metre40393910075243
186954
(N)HXH FE180 E30-E60 3 x 25 + 1 x 1625+1623.987413571.73stranded3LPEby the metre40393910075250
186957
(N)HXH FE180 E30-E60 3 x 353524.9100815291.80strandedLNPEby the metre40393910075229
186956
(N)HXH FE180 E30-E60 3 x 35 + 1 x 1635+1625.9116216931.93stranded3LPEby the metre40393910075236
186959
(N)HXH FE180 E30-E60 3 x 505028.2144020262.24strandedLNPEby the metre40393910075205
186958
(N)HXH FE180 E30-E60 3 x 50 + 1 x 2550+2529.9168023112.52stranded3LPEby the metre40393910075212
186961
(N)HXH FE180 E30-E60 3 x 707032.72016281432.7strandedLNPEby the metre40393910075182
186960
(N)HXH FE180 E30-E60 3 x 70 + 1 x 3570+3534235231463.07stranded3LPEby the metre40393910075199
186962
(N)HXH FE180 E30-E60 3 x 95 + 1 x 2095+5039.3321642964.18stranded3LPEby the metre40393910075175
186963
(N)HXH FE180 E30-E60 3 x 120 + 1 x 70120+7042.64098.2852554.74stranded3LPEby the metre40393910075168
186964
(N)HXH FE180 E30-E60 3 x 150 + 1 x 70150+7046.6499263615.63stranded3LPEby the metre40393910075151
186965
(N)HXH FE180 E30-E60 3 x 185 + 1 x 90185+9552624079506.99stranded3LPEby the metre40393910075144
186930
(N)HXH-J FE180 E30-E60 4 x 1.51.512.4582330.61solid3LPEby the metre40393910075496
186931
(N)HXH-J FE180 E30-E60 4 x 2.52.513.4962900.69solid3LPEby the metre40393910075489
186932
(N)HXH-J FE180 E30-E60 4 x 4414.61543810.78solid3LPEby the metre40393910075472
186933
(N)HXH-J FE180 E30-E60 4 x 6615.82304860.90solid3LPEby the metre40393910075465
186934
(N)HXH-J FE180 E30-E60 4 x 101017.83846881.07solid3LPEby the metre40393910075458
186967
(N)HXH FE180 E30-E60 4 x 161621.161410051.40stranded3LPEby the metre40393910075120
186968
(N)HXH FE180 E30-E60 4 x 252524.896014791.86stranded3LPEby the metre40393910075113
186969
(N)HXH FE180 E30-E60 4 x 353527.4134419292.15stranded3LPEby the metre40393910075106
186970
(N)HXH FE180 E30-E60 4 x 505031.5192025982.79stranded3LPEby the metre40393910075090
186971
(N)HXH FE180 E30-E60 4 x 707036.2268835783.38stranded3LPEby the metre40393910075083
186972
(N)HXH FE180 E30-E60 4 x 959541.7364847774.68stranded3LPEby the metre40393910075076
187532
(N)HXH FE180 E30-E60 4x959541.7364847774.68stranded3LNby the metre40393910073713
186973
(N)HXH FE180 E30-E60 4 x 12012044.6460858375.19stranded3LPEby the metre40393910075069
186974
(N)HXH FE180 E30-E60 4 x 15015050576073616.52stranded3LPEby the metre40393910075052
187548
(N)HXH-J FE180 E30-E60 4 x 18518555.3710490667.98stranded3LPEby the metre40393910073652
187077
(N)HXH FE180 E30-E60 4 x 24024062.992161186310.05stranded3LPEby the metre40393910074727
186935
(N)HXH-J FE180 E30-E60 5 x 1.51.513.4722760.71solid3LNPEby the metre40393910075441
186936
(N)HXH-J FE180 E30-E60 5 x 2.52.514.51203460.81solid3LNPEby the metre40393910075434
186937
(N)HXH-J FE180 E30-E60 5 x 4415.81924570.93solid3LNPEby the metre40393910075427
186938
(N)HXH-J FE180 E30-E60 5 x 6617.22885841.05solid3LNPEby the metre40393910075410
186939
(N)HXH-J FE180 E30-E60 5 x 101019.34808241.25solid3LNPEby the metre40393910075403
186975
(N)HXH FE180 E30-E60 5 x 161623.176812201.67stranded3LNPEby the metre40393910075045
186976
(N)HXH FE180 E30-E60 5 x 252527.2120018032.22stranded3LNPEby the metre40393910075038
186977
(N)HXH FE180 E30-E60 5 x 353530.5168023852.66stranded3LNPEby the metre40393910075021
186978
(N)HXH FE180 E30-E60 5 x 505034.8240031913.41stranded3LNPEby the metre40393910075014
186979
(N)HXH FE180 E30-E60 5 x 707040336043914.26stranded3LNPEby the metre40393910075007
190587
(N)HXH FE180 E30-E60 5 x 959546.6456059075.89stranded3LNPEby the metre40393910070613
196283
(N)HXH FE180 E30-E60 6x1010215769731434solid5LPEby the metre40393910061512
171272
(N)HXH-J FE180 E30-E60 7 x 1.51.514.41013290.81solid6LPEby the metre40393910079036
171273
(N)HXH-J FE180 E30-E60 7 x 2.52.515.61684190.92solid6LPEby the metre40393910079029
191080
(N)HXH-J FE180 E30-E60 7 x 6618.64037251.17solid5LNPEby the metre40393910069914
171279
(N)HXH-J FE180 E30-E60 12 x 1.51.518.31735121.20solid11LPEby the metre40393910078961
171280
(N)HXH-J FE180 E30-E60 12 x 2.52.5202886711.37solid11LPEby the metre40393910078954
171283
(N)HXH-J FE180 E30-E60 19 x 1.51.521.22747141.63solid18LPEby the metre40393910078923
171284
(N)HXH-J FE180 E30-E60 19 x 2.52.523.24569471.83solid18LPEby the metre40393910078916
171285
(N)HXH-J FE180 E30-E60 24 x 1.51.524.63469001.99solid23LPEby the metre40393910078909
171286
(N)HXH-J FE180 E30-E60 24 x 2.52.52757611992.27solid23LPEby the metre40393910078893
171287
(N)HXH-J FE180 E30-E60 30 x 1.51.52643210562.28solid29LPEby the metre40393910078886
171288
(N)HXH-J FE180 E30-E60 30 x 2.52.528.872014302.68solid29LPEby the metre40393910078879

Technical specifications

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. System Circuit Integrity is provided up to 400 V operating voltage. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (single core) 15 x D
Minimum bending during installation (multi core) 12 x D
Remarks bending radius 50% reduction if installation at 30°C and with a template
Circuit integrity FE 180
System circuit integrity E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 4000
Nominal voltage 0.6/1kV
* System Circuit Integrity is dependent on installation method
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Core colours CENELEC HD 308 S2, VDE 0293
Filler Flame retardant, halogen-free thermoplastic compound
Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Outer sheath colour orange
Circuit integrity IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020 (Rf1), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1
System circuit integrity DIN 4102-12, AREI-RGIE Section 4.3.3 FR2, NBN 713-020 (Rf1)
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1, SEV TP 20B/3C 3.4.1.1
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Section 4.3.3 F2, SEV TP 20B/3C 3.4.1.3

Documentation