(N)HXCH FE180 E90 B2ca
Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6
1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH






Product variants & stock
Article No. | Stock | Product | Reaction to fire | Outer sheath colour | Number of cores | Diameter mm² | Outer sheath diameter [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Conductor | Construction | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
18740800BZ | (N)HXCH FE180 E90 3 x 50/25 | B2ca-s1a,d1,a1 | orange | 3 | 50/25 | 32.5 | 1723 | 2545 | 2.729 | stranded | 3L | by the metre | 40393910036961 | |
19648300BZ | (N)HXCH FE180 E90 3 x 50/50 | B2ca-s1a,d1,a1 | orange | 3 | 50/50 | 34.3 | 1933 | 2932 | 3.028 | stranded | 3L | by the metre | ||
18607100BZ | (N)HXCH FE180 E90 3 x 1.5/1.5 | B2ca-s1a,d1,a1 | orange | 3 | 1.5/1.5 | 13.2 | 66 | 246 | 0.599 | solid | 3L | by the metre | 40393910039795 | |
18619500BZ | (N)HXCH FE180 E90 3 x 2.5/2.5 | B2ca-s1a,d1,a1 | orange | 3 | 2.5/2.5 | 14.1 | 104 | 303 | 0.784 | solid | 3L | by the metre | 40393910039207 | |
18619700BZ | (N)HXCH FE180 E90 3 x 4/4 | B2ca-s1a,d1,a1 | orange | 3 | 4/4 | 15.6 | 161 | 400 | 0.771 | solid | 3L | by the metre | 40393910039184 | |
18727800BZ | (N)HXCH FE180 E90 3 x 6/6 | B2ca-s1a,d1,a1 | orange | 3 | 6/6 | 16.9 | 240 | 521 | 0.921 | solid | 3L | by the metre | 40393910037173 | |
17241700BZ | (N)HXCH FE180 E90 3 x 35/16 | B2ca-s1a,d1,a1 | orange | 3 | 35/16 | 29 | 1190 | 1941 | 2.267 | stranded | 3L | by the metre | 40393910043600 | |
19648200BZ | (N)HXCH FE180 E90 3 x 35/35 | B2ca-s1a,d1,a1 | orange | 3 | 35/35 | 30.9 | 1358 | 2203 | 2.484 | stranded | 3L | by the metre | ||
18740900BZ | (N)HXCH FE180 E90 3 x 70/35 | B2ca-s1a,d1,a1 | orange | 3 | 70/35 | 37.6 | 2410 | 3536 | 3.542 | stranded | 3L | by the metre | 40393910036954 | |
18741000BZ | (N)HXCH FE180 E90 3 x 95/50 | B2ca-s1a,d1,a1 | orange | 3 | 95/50 | 41.9 | 3296 | 4581 | 4.285 | stranded | 3L | by the metre | 40393910036947 | |
18741100BZ | (N)HXCH FE180 E90 3 x 120/70 | B2ca-s1a,d1,a1 | orange | 3 | 120/70 | 45.3 | 4236 | 5688 | 5.112 | stranded | 3L | by the metre | 40393910036930 | |
18741200BZ | (N)HXCH FE180 E90 3 x 150/70 | B2ca-s1a,d1,a1 | orange | 3 | 150/70 | 50 | 5100 | 6911 | 5.889 | stranded | 3L | by the metre | 40393910036923 | |
18607200BZ | (N)HXCH FE180 E90 4 x 1.5/1.5 | B2ca-s1a,d1,a1 | orange | 4 | 1.5/1.5 | 14.1 | 81 | 280 | 0.677 | solid | 3LN | by the metre | 40393910039788 | |
18619600BZ | (N)HXCH FE180 E90 4 x 2.5/2.5 | B2ca-s1a,d1,a1 | orange | 4 | 2.5/2.5 | 15.1 | 128 | 350 | 0.754 | solid | 3LN | by the metre | 40393910039191 | |
18619800BZ | (N)HXCH FE180 E90 4 x 4/4 | B2ca-s1a,d1,a1 | orange | 4 | 4/4 | 16.7 | 200 | 464 | 0.87 | solid | 3LN | by the metre | 40393910039177 | |
18619900BZ | (N)HXCH FE180 E90 4 x 6/6 | B2ca-s1a,d1,a1 | orange | 4 | 6/6 | 18.1 | 297 | 612 | 1.051 | solid | 3LN | by the metre | 40393910039160 | |
18620000BZ | (N)HXCH FE180 E90 4 x 10/10 | B2ca-s1a,d1,a1 | orange | 4 | 10/10 | 20.1 | 504 | 858 | 1.25 | solid | 3LN | by the metre | 40393910039153 | |
18613100BZ | (N)HXCH FE180 E90 4 x 16/16 | B2ca-s1a,d1,a1 | orange | 4 | 16/16 | 25.3 | 796 | 1396 | 1.772 | stranded | 3LN | by the metre | 40393910039764 | |
18613200BZ | (N)HXCH FE180 E90 4 x 25/16 | B2ca-s1a,d1,a1 | orange | 4 | 25/16 | 28.9 | 1142 | 1895 | 2.568 | stranded | 3LN | by the metre | 40393910039757 | |
18613300BZ | (N)HXCH FE180 E90 4 x 35/16 | B2ca-s1a,d1,a1 | orange | 4 | 35/16 | 31.6 | 1526 | 2378 | 2.568 | stranded | 3LN | by the metre | 40393910039740 | |
18613400BZ | (N)HXCH FE180 E90 4 x 50/25 | B2ca-s1a,d1,a1 | orange | 4 | 50/25 | 36.7 | 2203 | 3245 | 3.374 | stranded | 3LN | by the metre | 40393910039733 | |
18613500BZ | (N)HXCH FE180 E90 4 x 70/35 | B2ca-s1a,d1,a1 | orange | 4 | 70/35 | 41.3 | 3082 | 4371 | 4.08 | stranded | 3LN | by the metre | 40393910039726 | |
18613600BZ | (N)HXCH FE180 E90 4 x 95/50 | B2ca-s1a,d1,a1 | orange | 4 | 95/50 | 46.4 | 4208 | 5712 | 5.179 | stranded | 3LN | by the metre | 40393910039719 | |
18613700BZ | (N)HXCH FE180 E90 4 x 120/70 | B2ca-s1a,d1,a1 | orange | 4 | 120/70 | 50.1 | 5388 | 7078 | 5.858 | stranded | 3LN | by the metre | 40393910039702 | |
18613800BZ | (N)HXCH FE180 E90 4 x 150/70 | B2ca-s1a,d1,a1 | orange | 4 | 150/70 | 55.3 | 6540 | 8631 | 7.11 | stranded | 3LN | by the metre | 40393910039689 | |
18613900BZ | (N)HXCH FE180 E90 4 x 185/95 | B2ca-s1a,d1,a1 | orange | 4 | 185/95 | 60.8 | 8159 | 10727 | 8.61 | stranded | 3LN | by the metre | 40393910039665 | |
18614000BZ | (N)HXCH FE180 E90 4 x 240/120 | B2ca-s1a,d1,a1 | orange | 4 | 240/120 | 69.2 | 10546 | 13949 | 10.885 | stranded | 3LN | by the metre | 40393910039658 | |
18607302BZ | (N)HXCH FE180 E90 7 x 1.5/2.5 | B2ca-s1b,d1,a1 | orange | 7 | 1.5/2.5 | 16.1 | 133 | 390 | 0.884 | solid | 7L | by the metre | 40393910039771 | |
19109602BZ | (N)HXCH FE180 E90 7 x 2.5/2.5 | B2ca-s1b,d1,a1 | orange | 7 | 2.5/2.5 | 17.3 | 200 | 484 | 0.994 | solid | 7L | by the metre | 40393910031782 | |
18741502BZ | (N)HXCH FE180 E90 12 x 1.5/2.5 | B2ca-s1b,d1,a1 | orange | 12 | 1.5/2.5 | 20.2 | 205.8 | 589 | 1.308 | solid | 12L | by the metre | 40393910036916 |
Technical specifications
Permitted operating temperature at conductor of +90˚C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
Circuit integrity | FE 180 |
---|---|
System circuit integrity | E90 |
Installation temperature | -5 °C - +50 °C |
Operating temperature | -45 °C - +90 °C |
Test voltage at 50Hz | 4000 |
---|---|
Nominal voltage | 0.6/1kV |
Minimum bending during installation (multi core) | 12 x D |
---|---|
Minimum bending radius permanent (multi core) | 12 x D |
System Circuit Integrity is dependent on installation method. |
For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines. |
Conductor | Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295) |
---|---|
Insulation | Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1" |
Core colours | CENELEC HD 308 S2, VDE 0293 |
Separator | Plastic tape |
Filler | Halogen-free compound or plastic tape |
Concentric conductor | Bare copper wires with reinforced helix |
Outer sheath material | Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4" |
Outer sheath colour | orange |
Circuit integrity | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
---|---|
System circuit integrity | DIN 4102-12, VdS 3423 (Single-core more than 16.0 mm²), AREI-RGIE Section 4.3.3 FR2 |
Reaction to fire | EN 13501-6 |
Euroclass | B2ca |
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD |
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1 |
Flame spread | IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2 |
Documentation
-
Datasheet
Download PDF [ 154.042 KB ]
-
Datasheet
Download PDF [ 152.748 KB ]
-
Datasheet
Download PDF [ 153.736 KB ]
-
Datasheet
Download PDF [ 153.903 KB ]
-
Datasheet
Download PDF [ 153.507 KB ]
-
Datasheet
Download PDF [ 152.961 KB ]
-
MPA Certificate
Download PDF [ 3.114 MB ]
-
CoC
Download PDF [ 500.449 KB ]
-
CoC
Download PDF [ 458.037 KB ]
-
VDE Certificate
Download PDF [ 336.451 KB ]