Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12
Fire behaviour according to EN 50575, EN 13601-6
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 1x2x0.8 mm
B2ca-s1a,d1,a1
2
8.8
15
99.8
0.256
by the metre
40393910230215
18811900BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0.8 mm
B2ca-s1a,d1,a1
2
9.3
25
125.3
0.295
by the metre
40393910230406
18812000BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0.8 mm
B2ca-s1a,d1,a1
2
12.2
45
190.4
0.437
by the metre
40393910230413
18812700BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0.8 mm
B2ca-s1a,d1,a1
2
18.4
85
420
0.964
by the metre
40393910230420
18812800BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0.8 mm
B2ca-s1a,d1,a1
2
19.3
126
492
1.070
by the metre
40393910230437
18812900BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0.8 mm
B2ca-s1a,d1,a1
2
23.3
206
681
1.412
by the metre
40393910230444
18834600BZ
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0.8 mm
B2ca-s1a,d1,a1
2
26.9
326
920.9
1.806
by the metre
40393910230475
Technical specifications
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
operating capacity, 1km @ 800Hz
120
Test voltage 50Hz, core/core
500
peak voltage
225
Capacitive coupling 0,8 mm, 100m @ 800Hz
200
Maximum loop resistance 0,8 mm
73.2
Minimum insulation resistance
100
Test voltage 50Hz, core/screen
2000
Circuit integrity
FE 180
System circuit integrity
E90
Installation temperature
-5 °C - +50 °C
Operating temperature
-30 °C - +70 °C
Minimum bending during installation (multi core)
7.5 x D
Minimum bending radius permanent (multi core)
7.5 x D
Minimal crush resistance / 10cm
1000
N
System Circuit Integrity dependent on installation method.
Conductor
Bare copper, solid, 0.8 mm diameter, VDE 0815
Insulation
Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Core colours
VDE 0815
Shielding
Al-laminated tape with copper drain wire Ø 0.8 mm
Inner sheath
Flame retardant polyolefin compound, VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM2"
Armouring (rodent protection)
Galvanised steel wire braid
Outer sheath material
Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"