FE180 E30
Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
in accordance to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
30 minutes system circuit integrity* with reference to DIN 4102-12
1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH






Product variants & stock
Download
Article No. | Stock | Product | Number of cores | Diameter mm² | Outer sheath diameter [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Conductor | Construction | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|
191118 | FE180 E30 2 x 1.5 | 2 | 1.5 | 7.8 | 29 | 102 | 0.22 | solid | LN | 40393910069662 | |
188360 | FE180 E30 2 x 1,5 | 2 | 1.5 | 7.8 | 29 | 102 | 0.22 | solid | 2L | 40393910072242 | |
191119 | FE180 E30 2 x 2.5 | 2 | 2.5 | 9 | 48 | 142 | 0.28 | solid | LN | 40393910069655 | |
190402 | FE180 E30 2 x 2,5 | 2 | 2.5 | 9 | 48 | 142 | 0.28 | solid | 2L | 40393910070996 | |
187180 | FE180 E30 3 x 1.5 | 3 | 1.5 | 8.3 | 43 | 121 | 0.25 | solid | LNPE | 40393910074499 | |
187184 | FE180 E30 3 x 2.5 | 3 | 2.5 | 9.5 | 72 | 169 | 0.31 | solid | LNPE | 40393910074451 | |
187187 | FE180 E30 3 x 4 | 3 | 4 | 11 | 115 | 243 | 0.41 | solid | LNPE | 40393910074420 | |
187189 | FE180 E30 3 x 6 | 3 | 6 | 12.5 | 173 | 329 | 0.51 | solid | LNPE | 40393910074406 | |
187182 | FE180 E30 4 x 1.5 | 4 | 1.5 | 9.1 | 58 | 147 | 0.29 | solid | 3LPE | 40393910074475 | |
190502 | FE180 E30 4 x 2.5 | 4 | 2.5 | 10.5 | 96 | 209 | 0.38 | solid | 3LPE | 40393910070828 | |
192352 | FE180 E30 4 x 4 | 4 | 4 | 12.2 | 154 | 304 | 0.49 | solid | 3LPE | 40393910067705 | |
192353 | FE180 E30 4 x 6 | 4 | 6 | 13.8 | 230 | 409 | 0.61 | solid | 3LPE | 40393910067699 | |
187183 | FE180 E30 5 x 1.5 | 5 | 1.5 | 9.9 | 72 | 177 | 0.35 | solid | 3LNPE | 40393910074468 | |
187186 | FE180 E30 5 x 2.5 | 5 | 2.5 | 11.6 | 120 | 255 | 0.47 | solid | 3LNPE | 40393910074437 | |
187188 | FE180 E30 5 x 4 | 5 | 4 | 13.4 | 192 | 371 | 0.61 | solid | 3LNPE | 40393910074413 | |
187190 | FE180 E30 5 x 6 | 5 | 6 | 15.2 | 288 | 504 | 0.76 | solid | 3LNPE | 40393910074390 | |
186267 | FE180 E30 7 x 1.5 | 7 | 1.5 | 10.8 | 100.8 | 220 | 0.41 | solid | 6LPE | 40393910076172 | |
186268 | FE180 E30 7 x 2.5 | 7 | 2.5 | 12.5 | 168 | 319 | 0.53 | solid | 6LPE | 40393910076165 | |
187201 | FE180 E30 7 x 6 | 7 | 6 | 16.7 | 403 | 644 | 0.89 | solid | 6LPE | 40393910074338 | |
187108 | FE180 E30 8 x 1.5 | 8 | 1.5 | 11.9 | 115 | 258 | 0.48 | solid | 7LPE | 40393910074680 | |
188345 | FE180 E30 10 x 1.5 | 10 | 1.5 | 13.8 | 144 | 319 | 0.69 | solid | 9LPE | 40393910072372 | |
186269 | FE180 E30 12 x 1.5 | 12 | 1.5 | 14.2 | 172.8 | 364 | 0.66 | solid | 11LPE | 40393910076158 | |
192479 | FE180 E30 12 x 2.5 | 12 | 2.5 | 16.7 | 288 | 536 | 0.88 | solid | 11LPE | 40393910067354 | |
187109 | FE180 E30 21 x 1.5 | 21 | 1.5 | 17.7 | 303 | 578 | 0.99 | solid | 20LPE | 40393910074673 | |
190412 | FE180 E30 27 x 1.5 | 27 | 1.5 | 20.4 | 389 | 752 | 1.30 | solid | 26LPE | 40393910070972 |
Technical specifications
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) | 12 x D |
---|---|
Minimum bending during installation (single core) | 15 x D |
Minimum bending radius permanent (single core) | 15 x D |
Minimum bending during installation (multi core) | 12 x D |
Remarks bending radius | 50% reduction if installation at 30°C and with a template |
Circuit integrity | FE 180 |
---|---|
System circuit integrity | E30 |
Installation temperature | -5 °C - +50 °C |
Operating temperature | -45 °C - +90 °C |
Test voltage at 50Hz | 3500 |
---|---|
Nominal voltage | 0.6/1kV |
System Circuit Integrity is depemndent on installation method. |
Conductor | Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295) |
---|---|
Insulation | Special compound, HD 604 S1 part 5 H |
Core colours | CENELEC HD 308 S2 |
Filler | HD 604 S1 part 5 H |
Outer sheath material | Compound, HD 604 S1 part 5 H |
Circuit integrity | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
---|---|
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD, SEV TP 20B/3C 3.4.3 |
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA, SEV TPV11 |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1, SEV TP 20B/3C 3.4.1.1 |
Flame spread | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Section 4.3.3 F2, SEV TP 20B/3C 3.4.1.3 |