Distribution box E30-E90

Type Hercules distribution box

Hercules distribution box
E30-E90

Product variants & stock

Article No. Stock ProductOuter dimensions (HxWxD)Inner dimensionsTop hat rail / frameWeight [kg]Packing unitGTIN / EAN
301382
Hercules cover AHD E30-E90340 mm x 380 mm x 170 mm260 mm x 300 mm x 130 mmempty, without base12.75 kg1 pc.40393910193077
301375
Hercules distribution box E30-E90 with top hat rail340 mm x 380 mm x 220 mm260 mm x 300 mm x 130 mm35 x 7.5 1-row16.58 kg1 pc.40393910193145
301376
Hercules distribution box E30-E90 with top hat rail430 mm x 380 mm x 220 mm350 mm x 300 mm x 130 mm35 x 7.5 2-rows20.06 kg1 pc.40393910193138
301377
Hercules distribution box E30-E90 with top hat rail600 mm x 380 mm x 220 mm520 mm x 300 mm x 130 mm35 x 7.5, 3-rows25.6 kg1 pc.40393910193121
301378
Hercules distribution box E30-E90 with QSA trough340 mm x 380 mm x 220 mm260 mm x 300 mm x 130 mm156 x 105 x 50 (6 strips)18 kg1 pc.40393910193114
301379
Hercules distribution box E30-E90 with QSA trough430 mm x 380 mm x 220 mm350 mm x 300 mm x 130 mm291 x 105 x 50 (11 strips)19.8 kg1 pc.40393910193107
301380
Hercules distribution box E30-E90 with QSA trough600 mm x 380 mm x 220 mm520 mm x 300 mm x 130 mm359 x 105 x 50 (13 strips)26.5 kg1 pc.40393910193091
1300467
Fire protection filler SP cartridge (310 ml)0.4 kg400 g cartridge40393910210804

Technical specifications

Distribution box or cover for power current and low current in accordance with DIN 4102-12 to protect commercial distribution/branch boxes and sub-distribution boxes against the effects of fire for a period of 30 or 90 minutes (System Circuit Integrity class E30 or E90), e.g. emergency lighting, alarm circuits and fire announcement systems, fire alarm systems, etc.
The Hercules distribution box or cover E30-E90 can be used for all Datwyler Keram cable types (N)HXH / (N)HXCH FE 180/E30-E60, (N)HXH / (N)HXCH FE 180/E90, JE-H(ST)H FE180/E30-E90, JE-H(ST)HRH FE180/E30-E90.
The time required for assembly is about 10 minutes. The screws are screwed into predrilled holes without plugs. The cable inlets and outlets are sealed with the fire protection filler.
Hercules cover box E30-E90 Typ AHD...
with mounting angles, screws, cartridge of fire protection filler.
Hercules distribution box E30-E90 Typ HS... (power current distribution box)
with mounting screws, cartridge of fire protection filler, top hat rail 35 x 7.5 x 250 mm.
Hercules distribution box E30-E90 Typ HI... (low current distribution box)
with mounting screws, cartridge of fire protection filler, QSA back mount frame ... x 105 x 50 mm. (Quante: depth 30 mm, pitch: 27.5 mm)
Please note that due to the selectivity of safety circuits or in the case of a decrease in cross section, a corresponding circuit breaker must be installed.

Documentation