Safety cable, 0.6/1kV, Keram
Halogen-free, with improved fire characteristics;
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
System Circuit Integrity is provided up to 400 V operating voltage.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core)
12 x D
Minimum bending during installation (single core)
15 x D
Minimum bending radius permanent (single core)
15 x D
Minimum bending during installation (multi core)
12 x D
Remarks bending radius
50% reduction if installation at 30°C and with a template
Circuit integrity
FE 180
System circuit integrity
E30-E60*
Installation temperature
-5 °C - +50 °C
Operating temperature
-45 °C - +90 °C
Test voltage at 50Hz
3500
Nominal voltage
0.6/1kV
* System Circuit Integrity is dependent on installation method
Conductor
Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Insulation
Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Core colours
CENELEC HD 308 S2(≥16 mm2: CENELEC HD 308 S2, VDE 0293)
Filler
HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Outer sheath material
Compound, HD 604 S1 part 5 H(16 mm2: polyolefin compound in accordance with VDE 0276-604, CENELEC HD 604 S1 "HM4", flame-retardant)