Product variants & stock

Article No. Stock ProductWeight [kg]Packing unitGTIN / EAN
476139
MD-DCS MTP module, 2x MTP on 6x LCQ/PC, OM50.16 kg1 pc.40393910232080

Technical specifications

Polycarbonate (PC) housing with press-fit cover (sealed). At the rear these MD-DCS modules have two MTP adapters which is routed to the front adapters (6x LCQ) with two internal module fanouts.
System MD-DCS
Fully equipped yes
Acceptance capacity 24 fibres
Fibre colour code IEC 60304
Adapter, front side 6 x LCQ/PC, light green
Adapter material, front side Polymeric
Dust protection, front side yes
Laser protection, front side no
Dust/Laser protection, front side Dust plug
Sleeve material, front side Zirconia (ZrO2)
Connectors, front side 24 x LC/PC 0°
Ferrule material, front side Zirconia (ZrO2)
Adapter, rear side 2 x MTP, black, Type A (key up/key down)
Adapter material, rear side Polythermide
Adapter type, rear side Type A (key up/key down)
Dust protection, rear side yes
Laser protection, rear side no
Dust/Laser protection, rear side Dust plug
Connectors, rear side 2 x MTP12 female Elite PC 0°
Ferrule material, rear side Polyphenylene sulfide resin
Housing, equipped with 6x LCQ adapters with ceramic sleeves on the front.
Rear fitted with 2 MTP adapters (Type A).
2 module fanouts (HighP): each with 12 fibres, 1x MTP Elite® (female) on 12x LC (ceramic ferrules).
MD-DCS MTP® modules are suitable for all high-density and high-performance applications with duplex signals, particularly in the data centre environment.
They find modular application in the slots of the MD-DCS modular panels (19”/1U) in which they can be inserted from the front.
They are used to accept pre-assembled MTP trunk cables.
Packing densities of up to 96 fibres on 1U are achieved with these modules.
They are assembled to a very high quality and guarantee optimum values for optical performance (IL/RL).
Insertion loss (IL), maximal, front side 0.25 dB
Insertion loss (IL), typical, front side 0.15 dB
Return loss (RL), minimal, front side 35 dB
Return loss (RL), typical, front side 40 dB
Insertion loss (IL), maximal, rear side 0.25 dB
Insertion loss (IL), typical, rear side 0.15 dB
Return loss (RL), minimal, back side 35 dB
Return loss (RL), typical, back side 45 dB
Fibre type G50/125 OM5
LC standard (IEC) IEC 61754-20
MTP standard (IEC) IEC 61754-7, IEC 61755-3-31, IEC 61755-3-32