CU 7120 4P / 2x4P F8
Data cable, S/FTP, Category 7A, AWG 22, Euroklasse Cca
1300 MHz
1 Inner conductor: AWG22 Bare copper wire
2 PE insulated conductor: 1.5 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Outer sheath: FRNC/LSOH











Product variants & stock
Download
Article No. | Stock | Product | Reaction to fire | Dimensions n x p x [mm (AWG)] | Outer sheath dimensions [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|
19146702CL | CU 7120 2x4P | Cca-s1b,d1,a1 | 2 x (4 x 2 x 0.59 (AWG22)) | 7.6 x 16.0 | 64.6 | 124 | 0.36 | 500 m drum | 40393910030426 | |
19146600CK | CU 7120 4P | Cca-s1a,d1,a1 | 4 x 2 x 0.59 (AWG22) | 7.3 | 32.3 | 55.9 | 0.154 | 1000 m drum | 40393910030563 |
Technical specifications
Electrically and mechanically advanced quality Cat.7A data cable - fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-9-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Reduced outer diameter.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Reduced outer diameter.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Minimum bending radius (during installation) | 60 mm |
---|---|
Tensile strength (2x4P) | 220 N |
Tensile strength (4P) | 110 N |
Minimum number of impacts | 10 |
Minimal crush resistance / 10cm | 1000 N |
AWG | 22 |
Solid / Flex | Solid wire |
Minimum bending radius (permanently installed) | 30 mm |
Data cable for structured premises cabling. For the transmission of digital and analogue voice, video and data signals. Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with ISO/IEC 11801-4. Applicable for Power over Ethernet PoE / PoE+ / 4PPoE up to 100W. |
Category | Cat.7A |
---|---|
GBit/s | Up to 10 Gbit/s |
Loop resistance at 20 °C | 131 Ω/km |
Operating capacity | 44 pF/m |
Impedance at 100 MHz, ±5Ω | 100 Ω |
NVP % | 76 |
Delay skew | 14 ns/100 m |
Shielding | shielded |
Near end unbalance attenuation LCL at 1-600 MHz | 40 dB |
Transfer impedance 1/10/30 MHz | < 5/5/8 mΩ/m |
Coupling attenuation | 85 dB |
Segregation class | d |
Installation temperature | 0 °C - +50 °C |
---|---|
Operating temperature | -20 °C - +60 °C |
Wire colour | white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708 |
Imprint | DATWYLER «cable type» «additional text» «batch number» «meter marks» |
Field of application | Indoor |
Reaction to fire | EN 13501-6 |
---|---|
Euroclass | Cca |
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD |
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1 |
Flame spread | IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Section 4.3.3 F2 |
Cables standard | ISO/IEC 61156-5, EN 50288-9-1 |
Conductor Diameter (AWG) | according to UL444, table 5 |
Cat./Class | Cat.7A / Class FA |
PoE | IEEE 802.3bt Type 4 (100W) |
Outer sheath material | FRNC/LSZH |
---|---|
Outer sheath colour | orange |
Documentation
-
Datasheet
Download PDF [ 195.994 KB ]
-
Datasheet
Download PDF [ 195.754 KB ]
-
Datasheet
Download PDF [ 196.425 KB ]
-
Datasheet
Download PDF [ 196.771 KB ]
-
Datasheet
Download PDF [ 196.949 KB ]
-
Datasheet
Download PDF [ 196.235 KB ]
-
Transmission Parameter
Download PDF [ 540.269 KB ]
-
GHMT PVP Certificates
Download PDF [ 248.094 KB ]
-
GHMT PVP Certificates
Download PDF [ 229.077 KB ]