(N)HXCH FE180 E90 B2ca

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

Description

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.

  • For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
  • Outer sheath colour orange
  • Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
  • Concentric conductor Bare copper wires with reinforced helix
  • Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
  • Core colours CENELEC HD 308 S2, VDE 0293
  • Filler Halogen-free compound or plastic tape
  • Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
  • Test voltage at 50Hz 4000 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -45 °C - +90 °C
  • Minimum bending during installation (multi core) 12 x D
  • Minimum bending radius permanent (multi core) 12 x D
  • System Circuit Integrity is dependent on installation method.
  • Reaction to fire (Euroclasses) EN 13501-6: B2ca
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Flame Spread IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
  • Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • System circuit integrity DIN 4102-12, VdS 3423 (Single-core more than 16.0 mm²), AREI-RGIE Art.104-FR2
  • Circuit Integrity (FE180) IEC 60331-11/-21 (180 minutes),VDE 0472-814 (FE180),IEC 60331-1 (120 minutes),IEC 60331-2 (120 minutes),EN 50200 (PH120 minutes),VDE 0482-200 (PH120),VDE 0482-362,AREI-RGIE Art.104-FR1

Documentation

ENDENLFRCNESIT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet
MPA Certificate file-icon MPA Certificate file-icon file-icon file-icon file-icon file-icon
VDE Certificate VDE Certificate file-icon file-icon file-icon file-icon file-icon file-icon

Versions

Article No.StockProductReaction To FireOuter sheath colourNumber of CoresDiameter mm²Outer sheath diameter [mm]CU rate [kg\km]Weight [kg\km]Fire load [kWh\m]ConductorConstructionPacking unit
18607100BZ (N)HXCH FE180 E90 3 x 1.5/1.5B2ca-s1a,d1,a1orange31.5/1.513.2 mm66 kg/km2480.599 kWh/msolid3Lby the metre
18619500BZ (N)HXCH FE180 E90 3 x 2.5/2.5B2ca-s1a,d1,a1orange32.5/2.514.1 mm104 kg/km3050.784 kWh/msolid3Lby the metre
18619700BZ (N)HXCH FE180 E90 3 x 4/4B2ca-s1a,d1,a1orange34/415.6 mm161 kg/km4010.771 kWh/msolid3Lby the metre
18727800BZ (N)HXCH FE180 E90 3 x 6/6B2ca-s1a,d1,a1orange36/616.9 mm240 kg/km5250.921 kWh/msolid3Lby the metre
17241700BZ (N)HXCH FE180 E90 3 x 35/16B2ca-s1a,d1,a1orange335/1629 mm1190 kg/km19442.267 kWh/mstranded3Lby the metre
18740800BZ (N)HXCH FE180 E90 3 x 50/25B2ca-s1a,d1,a1orange350/2532.5 mm1723 kg/km25492.729 kWh/mstranded3Lby the metre
18740900BZ (N)HXCH FE180 E90 3 x 70/35B2ca-s1a,d1,a1orange370/3537.6 mm2410 kg/km35403.542 kWh/mstranded3Lby the metre
18741000BZ (N)HXCH FE180 E90 3 x 95/50B2ca-s1a,d1,a1orange395/5041.9 mm3296 kg/km46044.285 kWh/mstranded3Lby the metre
18741100BZ (N)HXCH FE180 E90 3 x 120/70B2ca-s1a,d1,a1orange3120/7045.3 mm4236 kg/km56945.112 kWh/mstranded3Lby the metre
18741200BZ (N)HXCH FE180 E90 3 x 150/70B2ca-s1a,d1,a1orange3150/7050 mm5100 kg/km69195.889 kWh/mstranded3Lby the metre
18607200BZ (N)HXCH FE180 E90 4 x 1.5/1.5B2ca-s1a,d1,a1orange41.5/1.514.1 mm81 kg/km2830.677 kWh/msolid3LNby the metre
18619600BZ (N)HXCH FE180 E90 4 x 2.5/2.5B2ca-s1a,d1,a1orange42.5/2.515.1 mm128 kg/km3510.754 kWh/msolid3LNby the metre
18619800BZ (N)HXCH FE180 E90 4 x 4/4B2ca-s1a,d1,a1orange44/416.7 mm200 kg/km4660.87 kWh/msolid3LNby the metre
18619900BZ (N)HXCH FE180 E90 4 x 6/6B2ca-s1a,d1,a1orange46/618.1 mm297 kg/km6181.051 kWh/msolid3LNby the metre
18620000BZ (N)HXCH FE180 E90 4 x 10/10B2ca-s1a,d1,a1orange410/1020.1 mm504 kg/km8671.25 kWh/msolid3LNby the metre
18613100BZ (N)HXCH FE180 E90 4 x 16/16B2ca-s1a,d1,a1orange416/1625.3 mm796 kg/km13991.772 kWh/mstranded3LNby the metre
18613200BZ (N)HXCH FE180 E90 4 x 25/16B2ca-s1a,d1,a1orange425/1628.9 mm1142 kg/km18992.568 kWh/mstranded3LNby the metre
18613300BZ (N)HXCH FE180 E90 4 x 35/16B2ca-s1a,d1,a1orange435/1631.6 mm1526 kg/km23822.568 kWh/mstranded3LNby the metre
18613400BZ (N)HXCH FE180 E90 4 x 50/25B2ca-s1a,d1,a1orange450/2536.7 mm2203 kg/km32493.374 kWh/mstranded3LNby the metre
18613500BZ (N)HXCH FE180 E90 4 x 70/35B2ca-s1a,d1,a1orange470/3541.3 mm3082 kg/km43764.08 kWh/mstranded3LNby the metre
18613600BZ (N)HXCH FE180 E90 4 x 95/50B2ca-s1a,d1,a1orange495/5046.4 mm4208 kg/km57375.179 kWh/mstranded3LNby the metre
18613700BZ (N)HXCH FE180 E90 4 x 120/70B2ca-s1a,d1,a1orange4120/7050.1 mm5388 kg/km70855.858 kWh/mstranded3LNby the metre
18613800BZ (N)HXCH FE180 E90 4 x 150/70B2ca-s1a,d1,a1orange4150/7055.3 mm6540 kg/km86407.11 kWh/mstranded3LNby the metre
18613900BZ (N)HXCH FE180 E90 4 x 185/95B2ca-s1a,d1,a1orange4185/9560.8 mm8159 kg/km107378.61 kWh/mstranded3LNby the metre
18614000BZ (N)HXCH FE180 E90 4 x 240/120B2ca-s1a,d1,a1orange4240/12069.2 mm10546 kg/km1396110.885 kWh/mstranded3LNby the metre
18607302BZ (N)HXCH FE180 E90 7 x 1.5/2.5B2ca-s1b,d1,a1orange71.5/2.516.1 mm133 kg/km3930.884 kWh/msolid7Lby the metre
19109602BZ (N)HXCH FE180 E90 7 x 2.5/2.5B2ca-s1b,d1,a1orange72.5/2.517.3 mm200 kg/km4860.994 kWh/msolid7Lby the metre
18741502BZ (N)HXCH FE180 E90 12 x 1.5/2.5B2ca-s1b,d1,a1orange121.5/2.520.2 mm205.8 kg/km5951.308 kWh/msolid12Lby the metre
Additional dimensions available on request.