(N)HXH FE180 E30-E60 B2ca

Safety cable, 0.6/1kV, Keram
Halogen-free, with improved fire characteristics;
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH

06_Density 03_LS0H 05_Spread 08_System 04_Propagation 07_Circuit

Product variants & stock

Article No. Stock ProductReaction to fireOuter sheath colourDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionPacking unitGTIN / EAN
18628000BZ
(N)HXH FE180 E30-E60 2 x 1.5B2ca-s1a,d1,a1orange1.511291750.441solidLNby the metre40393910039122
18692400BZ
(N)HXH FE180 E30-E60 2 x 10B2ca-s1a,d1,a1orange1015.41924490.754solidLNby the metre40393910038156
18695200BZ
(N)HXH FE180 E30-E60 2 x 16B2ca-s1a,d1,a1orange1618.23076520.98solidLNby the metre40393910037791
18692100BZ
(N)HXH FE180 E30-E60 2 x 2.5B2ca-s1a,d1,a1orange2.511.8482120.495solidLNby the metre40393910038187
18692200BZ
(N)HXH FE180 E30-E60 2 x 4B2ca-s1a,d1,a1orange412.8772670.565solidLNby the metre40393910038170
18692300BZ
(N)HXH FE180 E30-E60 2 x 6B2ca-s1a,d1,a1orange613.81153290.636solidLNby the metre40393910038163
18692500BZ
(N)HXH-J FE180 E30-E60 3 x 1.5B2ca-s1a,d1,a1orange1.511.5431960.488solidLNPEby the metre40393910038149
18692900BZ
(N)HXH-J FE180 E30-E60 3 x 10B2ca-s1a,d1,a1orange1016.32885490.836solidLNPEby the metre40393910037999
18695300BZ
(N)HXH FE180 E30-E60 3 x 16B2ca-s1a,d1,a1orange1619.34618041.076strandedLNPEby the metre40393910037784
18692600BZ
(N)HXH-J FE180 E30-E60 3 x 2.5B2ca-s1a,d1,a1orange2.512.4722450.551solidLNPEby the metre40393910038071
18695500BZ
(N)HXH FE180 E30-E60 3 x 25B2ca-s1a,d1,a1orange2522.672011741.634strandedLNPEby the metre40393910037760
18695400BZ
(N)HXH FE180 E30-E60 3 x 25 + 1 x 16B2ca-s1a,d1,a1orange25+1623.987413521.576stranded3LPEby the metre40393910037777
18695700BZ
(N)HXH FE180 E30-E60 3 x 35B2ca-s1a,d1,a1orange3524.9100815161.634strandedLNPEby the metre40393910037746
18695600BZ
(N)HXH FE180 E30-E60 3 x 35 + 1 x 16B2ca-s1a,d1,a1orange35+1625.9116216811.787stranded3LPEby the metre40393910037753
18692700BZ
(N)HXH-J FE180 E30-E60 3 x 4B2ca-s1a,d1,a1orange413.51153150.63solidLNPEby the metre40393910038019
18695900BZ
(N)HXH FE180 E30-E60 3 x 50B2ca-s1a,d1,a1orange5028.2144020092.081strandedLNPEby the metre40393910037722
18695800BZ
(N)HXH FE180 E30-E60 3 x 50 + 1 x 25B2ca-s1a,d1,a1orange50+2529.9168022952.312stranded3LPEby the metre40393910037739
18692800BZ
(N)HXH-J FE180 E30-E60 3 x 6B2ca-s1a,d1,a1orange614.61733950.71solidLNPEby the metre40393910038002
18696100BZ
(N)HXH FE180 E30-E60 3 x 70B2ca-s1a,d1,a1orange7032.7201627892.613strandedLNPEby the metre40393910037708
18696000BZ
(N)HXH FE180 E30-E60 3 x 70 + 1 x 35B2ca-s1a,d1,a1orange70+3534235231202.807stranded3LPEby the metre40393910037715
18693000BZ
(N)HXH-J FE180 E30-E60 4 x 1.5B2ca-s1a,d1,a1orange1.512.4582300.572solid3LPEby the metre40393910037982
18693400BZ
(N)HXH-J FE180 E30-E60 4 x 10B2ca-s1a,d1,a1orange1017.83846820.992solid3LPEby the metre40393910037944
18696700BZ
(N)HXH FE180 E30-E60 4 x 16B2ca-s1a,d1,a1orange1621.161410011.277stranded3LPEby the metre40393910037654
18693100BZ
(N)HXH-J FE180 E30-E60 4 x 2.5B2ca-s1a,d1,a1orange2.513.4962900.634solid3LPEby the metre40393910037975
18696800BZ
(N)HXH FE180 E30-E60 4 x 25B2ca-s1a,d1,a1orange2524.896014731.695stranded3LPEby the metre40393910037647
18696900BZ
(N)HXH FE180 E30-E60 4 x 35B2ca-s1a,d1,a1orange3527.4134419161.951stranded3LPEby the metre40393910037630
18693200BZ
(N)HXH-J FE180 E30-E60 4 x 4B2ca-s1a,d1,a1orange414.61543770.724solid3LPEby the metre40393910037968
18697000BZ
(N)HXH FE180 E30-E60 4 x 50B2ca-s1a,d1,a1orange5031.5192025802.604stranded3LPEby the metre40393910037623
18693300BZ
(N)HXH-J FE180 E30-E60 4 x 6B2ca-s1a,d1,a1orange615.82304810.831solid3LPEby the metre40393910037951
18697100BZ
(N)HXH FE180 E30-E60 4 x 70B2ca-s1a,d1,a1orange7036.2268835543.199stranded3LPEby the metre40393910037616
18753200BZ
(N)HXH FE180 E30-E60 4 x 95B2ca-s1a,d1,a1orange9541.7364847524.357stranded3LNby the metre40393910036909
18693500BZ
(N)HXH-J FE180 E30-E60 5 x 1.5B2ca-s1a,d1,a1orange1.513.4722730.665solid3LNPEby the metre40393910037937
18693900BZ
(N)HXH-J FE180 E30-E60 5 x 10B2ca-s1a,d1,a1orange1019.34808191.164solid3LNPEby the metre40393910037890
18697500BZ
(N)HXH FE180 E30-E60 5 x 16B2ca-s1a,d1,a1orange1623.176812161.525stranded3LNPEby the metre40393910037579
18693600BZ
(N)HXH-J FE180 E30-E60 5 x 2.5B2ca-s1a,d1,a1orange2.514.51203460.754solid3LNPEby the metre40393910037920
18697600BZ
(N)HXH FE180 E30-E60 5 x 25B2ca-s1a,d1,a1orange2527.2120018002.055stranded3LNPEby the metre40393910037562
18697700BZ
(N)HXH FE180 E30-E60 5 x 35B2ca-s1a,d1,a1orange3530.5168023712.45stranded3LNPEby the metre40393910037555
18693700BZ
(N)HXH-J FE180 E30-E60 5 x 4B2ca-s1a,d1,a1orange415.81924530.863solid3LNPEby the metre40393910037913
18697800BZ
(N)HXH FE180 E30-E60 5 x 50B2ca-s1a,d1,a1orange5034.8240031732.974stranded3LNPEby the metre40393910037548
18693800BZ
(N)HXH-J FE180 E30-E60 5 x 6B2ca-s1a,d1,a1orange617.22885790.983solid3LNPEby the metre40393910037906
18697900BZ
(N)HXH FE180 E30-E60 5 x 70B2ca-s1a,d1,a1orange7040336043663.65stranded3LNPEby the metre40393910037531
17127200BZ
(N)HXH-J FE180 E30-E60 7 x 1.5B2ca-s1a,d1,a1orange1.514.41013270.758solid6LPEby the metre40393910043709
17127300BZ
(N)HXH-J FE180 E30-E60 7 x 2.5B2ca-s1a,d1,a1orange2.515.61684190.857solid6LPEby the metre40393910043693
17127900BZ
(N)HXH-J FE180 E30-E60 12 x 1.5B2ca-s1a,d1,a1orange1.518.31735061.128solid11LPEby the metre40393910043631
17128000BZ
(N)HXH-J FE180 E30-E60 12 x 2.5B2ca-s1a,d1,a1orange2.5202886631.288solid11LPEby the metre40393910043624
19040400BZ
(N)HXH FE180 E30-E60 2 x 25B2ca-s1a,d1,a1orange2521.24809371.281strandedLNby the metre40393910032833
18696300BZ
(N)HXH FE180 E30-E60 3 x 120 + 1 x 70B2ca-s1a,d1,a1orange120+7042.64098.2852224.419stranded3LPEby the metre40393910037685
18696400BZ
(N)HXH FE180 E30-E60 3 x 150 + 1 x 70B2ca-s1a,d1,a1orange150+7046.6499263205.244stranded3LPEby the metre40393910037678
18696500BZ
(N)HXH FE180 E30-E60 3 x 185 + 1 x 90B2ca-s1a,d1,a1orange185+9552624079036.505stranded3LPEby the metre40393910037661
18696200BZ
(N)HXH FE180 E30-E60 3 x 95 + 1 x 20B2ca-s1a,d1,a1orange95+5039.3321641933.893stranded3LPEby the metre40393910037692
18697300BZ
(N)HXH FE180 E30-E60 4 x 120B2ca-s1a,d1,a1orange12044.6460858004.831stranded3LPEby the metre40393910037593
18697400BZ
(N)HXH FE180 E30-E60 4 x 150B2ca-s1a,d1,a1orange15050576073136.103stranded3LPEby the metre40393910037586
18754800BZ
(N)HXH-J FE180 E30-E60 4 x 185B2ca-s1a,d1,a1orange18555.3710490087.404stranded3LPEby the metre40393910036862
18707700BZ
(N)HXH FE180 E30-E60 4 x 240B2ca-s1a,d1,a1orange24062.99216117879.4stranded3LPEby the metre40393910037364
18697200BZ
(N)HXH FE180 E30-E60 4 x 95B2ca-s1a,d1,a1orange9541.7364847524.357stranded3LPEby the metre40393910037609
19058700BZ
(N)HXH FE180 E30-E60 5 x 95B2ca-s1a,d1,a1orange9546.6456058905.035stranded3LNPEby the metre40393910032666
19257200BZ
(N)HXH FE180 E30-E60 2 x 1.5B2ca-s1a,d1,a1orange1.511291740.441solid2Lby the metre40393910027341
19258200BZ
(N)HXH FE180 E30-E60 2 x 2.5B2ca-s1a,d1,a1orange2.511.8482120.495solid2Lby the metre40393910027327

Technical specifications

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. System Circuit Integrity is provided up to 400 V operating voltage. Permitted operating temperature at conductor of +90˚C. Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (single core) 15 x D
Minimum bending during installation (multi core) 12 x D
Remarks bending radius 50% reduction if installation at 30°C and with a template
Circuit integrity (FE180) FE 180
System circuit integrity E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 4000
Nominal voltage 0.6/1kV
For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
* System Circuit Integrity is dependent on installation method
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Core colours CENELEC HD 308 S2, VDE 0293
Filler Flame retardant, halogen-free thermoplastic compound
Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Outer sheath colour orange
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-331-1 (PH120), AREI-RGIE Art.104-FR1
System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
Reaction to fire EN 13501-6
Euroclass B2ca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Art.104-F2

Documentation