FE180 E30 CL

Safety cable, 0.6/1kV, armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H

1 Conductor: solid / stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock ProductDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorGTIN / EAN
193886
FE180 E30 CL1.511432100.46solid40393910065367
187199
FE180 E30 CL2.512722550.50solid40393910074345
191121
FE180 E30 CL615.81734810.90solid40393910069648
188354
FE180 E30 CL10182886511.20solid40393910072303
191038
FE180 E30 CL2.5141203880.76solid40393910070040
188350
FE180 E30 CL4161924881.05solid40393910072341
188353
FE180 E30 CL617.52886401.28solid40393910072310
188397
FE180 E30 CL10214809641.76solid40393910072082
188355
FE180 E30 CL6194037941.53solid40393910072297
191097
FE180 E30 CL4141153730.69solid40393910069785
191595
FE180 E30 CL2.514962960.56solid40393910069143
187167
FE180 E30 CL4161544080.79solid40393910074512
188352
FE180 E30 CL6172305351.06solid40393910072327
187197
FE180 E30 CL2.5161684760.91solid40393910074369
188356
FE180 E30 CL102367212012.13solid40393910072280
192461
FE180 E30 CL1.5151154030.85solid40393910067477
187128
FE180 E30 CL2.5161924891.04solid40393910074642
191104
FE180 E30 CL4183086841.36solid40393910069754

Technical specifications

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (single core) 15 x D
Minimum bending during installation (multi core) 12 x D
Circuit integrity (FE180) FE 180
System circuit integrity E30
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 3500
Nominal voltage 0.6/1kV
* System Circuit Integrity is dependent on installation method
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Insulation Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Core colours CENELEC HD 308 S2
Filler HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Inner sheath Compound, HD 604 S1 part 5 H(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 ""HM 4"", flame-retardant)
Armouring (rodent protection) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Outer sheath material Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)
Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3

Documentation