Back to: Safety cables

FE180 E30 CL

Safety cable, 0.6/1kV, armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H

1 Conductor: solid / stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH

Description

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

  • Outer sheath material Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)
  • Armouring (rodent protection) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
  • Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
  • Core colours CENELEC HD 308 S2
  • Filler HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
  • Inner sheath Compound, HD 604 S1 part 5 H(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 ""HM 4"", flame-retardant)
  • Insulation Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
  • Test voltage at 50Hz 3500 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -45 °C - +90 °C
  • Minimum bending during installation (multi core) 12 x D
  • Minimum bending during installation (single core) 15 x D
  • Minimum bending radius permanent (multi core) 12 x D
  • Minimum bending radius permanent (single core) 15 x D
  • * System Circuit Integrity is dependent on installation method
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
  • Flame Propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
  • Flame Spread IEC 60332-3-24 Cat. C, EN 60332-3-24 Cat. C, VDE 0482-332-3-24 Cat. C, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3
  • Smoke Density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
  • System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
  • Circuit Integrity (FE180) IEC 60331-11/-21 (180 minutes),VDE 0472-814 (FE180),BS 6387 C/W/Z,IEC 60331-1 (120 minutes),IEC 60331-2 (120 minutes),EN 50200 (PH120 minutes),VDE 0482-200 (PH120),VDE 0482-362,AREI-RGIE Art.104-FR1

Documentation

ENDENLFRCNESIT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet

Versions

Article No.StockProductNumber of CoresDiameter mm²Outer sheath diameter [mm]CU rate [kg\km]Weight [kg\km]Fire load [kWh\m]Conductor
193886 FE180 E30 CL31.51143 kg/km2110.46 kWh/msolid
187199 FE180 E30 CL32.51272 kg/km2550.50 kWh/msolid
191097 FE180 E30 CL3414115 kg/km3730.69 kWh/msolid
191121 FE180 E30 CL3615.8173 kg/km4870.90 kWh/msolid
188354 FE180 E30 CL31018288 kg/km6551.20 kWh/msolid
191595 FE180 E30 CL42.51496 kg/km2960.56 kWh/msolid
187167 FE180 E30 CL4416154 kg/km4080.79 kWh/msolid
188352 FE180 E30 CL4617230 kg/km5391.06 kWh/msolid
191038 FE180 E30 CL52.514120 kg/km3880.76 kWh/msolid
188350 FE180 E30 CL5416192 kg/km4881.05 kWh/msolid
188353 FE180 E30 CL5617.5288 kg/km6431.28 kWh/msolid
188397 FE180 E30 CL51021480 kg/km9711.76 kWh/msolid
187197 FE180 E30 CL72.516168 kg/km4760.91 kWh/msolid
188355 FE180 E30 CL7619403 kg/km8011.53 kWh/msolid
188356 FE180 E30 CL71023672 kg/km12122.13 kWh/msolid
192461 FE180 E30 CL81.515115 kg/km4040.85 kWh/msolid
187128 FE180 E30 CL82.516192 kg/km4891.04 kWh/msolid
191104 FE180 E30 CL8418308 kg/km6841.36 kWh/msolid
Additional dimensions available on request