FO Universal ZGGFR Safety / U-DQ(ZN)BH

Safety cable E30*, up to 12 fibres
metal-free, water resistant, rodent protection,
in accordance with IEC 60332-1-2 and IEC 60332-3-24
30 minutes System Circuit Integrity* with reference to DIN 4102-12

1 ≤ 12 fibres
2 Flame retardant protective coating
3 Glass armour
4 Ripcord
5 FR/LS0H sheath

04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock Loose tube constructionFibres per loose tubeNumber of used loose tubesProductOuter sheath colourNumber of fibresFibre typeFibre categoryOuter sheath diameter [mm]Bending radius [mm]CU rate [kg/km]Weight [kg/km]Tensile load [N]Crush resistance short term [N]Crush resistance continuous [N]Fire load [kWh/m]Packing unitGTIN / EAN
187288
141FO Universal Safety 1x4red4E9/125 G.652.D OS2OS27.81200751000500020000.301by the metre40393910074024
190604
141FO Universal Safety 1x4red4G50/125 OM3OM37.81200751000500020000.301by the metre40393910070521
193447
141FO Universal Safety 1x4red4G50/125 OM4OM47.81200751000500020000.301by the metre40393910065527
191867
161FO Universal Safety 1x6red6E9/125 G.652.D OS2OS27.81200751000500020000.301by the metre40393910068610
191851
161FO Universal Safety 1x6red6G50/125 OM3OM37.81200751000500020000.301by the metre40393910068665
193448
161FO Universal Safety 1x6red6G50/125 OM4OM47.81200751000500020000.301by the metre40393910065510
196130
181FO Universal Safety 1x8red8E9/125 G.652.D OS2OS27.81200751000500020000.301by the metre40393910061642
196120
181FO Universal Safety 1x8red8G50/125 OM3OM37.81200751000500020000.301by the metre40393910061659
193449
181FO Universal Safety 1x8red8G50/125 OM4OM47.81200751000500020000.301by the metre40393910065503
190719
1121FO Universal Safety 1x12red12E9/125 G.652.D OS2OS27.81200751000500020000.301by the metre40393910070361
191796
1121FO Universal Safety 1x12red12G50/125 OM3OM37.81200751000500020000.301by the metre40393910068795
193450
1121FO Universal Safety 1x12red12G50/125 OM4OM47.81200751000500020000.301by the metre40393910065497

Technical specifications

Metal-free fibre optic safety cable with one central loose tube, up to 12 fibres. The optimal combination of flame retardant fibre coating and flame-inhibiting stabilizing elements ensures enhanced functional integrity (System Circuit Integrity*) in case of fire for 30 minutes (transmission of audio, video and 1Gbit/s signals approved by a certified test report).
Maximum number of fibres 12
System circuit integrity E30
Installation temperature -10 °C - +50 °C
Storage temperature -25 °C - +70 °C
Operating temperature -25 °C - +70 °C
Imprint DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»
Field of application Universal
Safety applications in tunnels, underground railways, banks, insurance companies, large-scale industry.
LAN backbone.
Indoor and outdoor cabling.
Can also be installed in cable platforms, trays, ducts and vertical shafts (without System Circuit Integrity*).
Can be spliced in FO distributors.
* System Circuit Integrity is dependent on installation method. Certified clamps, ducts, conduits, etc. are mandatory.
Tensile performance IEC 60794-1-21 E1
Crush resistance IEC 60794-1-21 E3
Impact IEC 60794-1-21 E4
Repeated bending IEC 60794-1-21 E6
Torsion IEC 60794-1-21 E7
Bend IEC 60794-1-21 E11
Temperature cycling IEC 60794-1-22 F1
Water penetration IEC 60794-1-22 F5
Circuit integrity IEC 60331-11, IEC 60331-25 (FE180), EN 50200 PH30, VDE 0482-200
System circuit integrity with reference to DIN 4102-12, VKF Fire Safety Application No. 24176
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
UV resistance EN 50289-4-17
Outer sheath material FRNC/LSZH

Documentation