(N)HXCH FE180 E30-E60 B2ca

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

07_Circuit 08_System 05_Spread 06_Density 03_LS0H 04_Propagation

Product variants & stock

Article No. Stock ProductReaction to fireOuter sheath colourNumber of coresDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionPacking unitGTIN / EAN
18694300BZ
(N)HXCH FE180 E30-E60 2 x 1.5/1.5B2ca-s1a,d1,a1orange21.5/1.512.7522210.551solidLNby the metre40393910037883
18694400BZ
(N)HXCH FE180 E30-E60 2 x 2.5/2.5B2ca-s1a,d1,a1orange22.5/2.513.5802690.612solidLNby the metre40393910037876
18723200BZ
(N)HXCH FE180 E30-E60 2 x 4/4B2ca-s1a,d1,a1orange24/414.91233500.706solidLNby the metre40393910037296
18723400BZ
(N)HXCH FE180 E30-E60 2 x 6/6B2ca-s1a,d1,a1orange26/6161824280.79solidLNby the metre40393910037289
18694500BZ
(N)HXCH FE180 E30-E60 3 x 1.5/1.5B2ca-s1a,d1,a1orange31.5/1.513.2662460.599solid3Lby the metre40393910037869
18694600BZ
(N)HXCH FE180 E30-E60 3 x 2.5/2.5B2ca-s1a,d1,a1orange32.5/2.514.11043030.784solid3Lby the metre40393910037852
18723800BZ
(N)HXCH FE180 E30-E60 3 x 16/16B2ca-s1a,d1,a1orange316/1621.3624.710271.348stranded3Lby the metre40393910037272
18723900BZ
(N)HXCH FE180 E30-E60 3 x 25/16B2ca-s1a,d1,a1orange325/162590214331.799stranded3Lby the metre40393910037265
18724000BZ
(N)HXCH FE180 E30-E60 3 x 35/16B2ca-s1a,d1,a1orange335/1637.3119017992.096stranded3Lby the metre40393910037258
18724100BZ
(N)HXCH FE180 E30-E60 3 x 50/25B2ca-s1a,d1,a1orange350/2531.7172324502.689stranded3Lby the metre40393910037241
18724200BZ
(N)HXCH FE180 E30-E60 3 x 70/35B2ca-s1a,d1,a1orange370/3536241033423.32stranded3Lby the metre40393910037234
18698500BZ
(N)HXCH FE180 E30-E60 3 x 95/50B2ca-s1a,d1,a1orange395/5041.1329644194.416stranded3Lby the metre40393910037524
18698600BZ
(N)HXCH FE180 E30-E60 3 x 120/70B2ca-s1a,d1,a1orange3120/7044.5423655245.002stranded3Lby the metre40393910037517
18698700BZ
(N)HXCH FE180 E30-E60 3 x 150/70B2ca-s1a,d1,a1orange3150/7049.2510067306.114stranded3Lby the metre40393910037500
18698800BZ
(N)HXCH FE180 E30-E60 3 x 240/120B2ca-s1a,d1,a1orange3240/12061.58242109089.391stranded3Lby the metre40393910037494
18694700BZ
(N)HXCH FE180 E30-E60 4 x 1.5/1.5B2ca-s1a,d1,a1orange41.5/1.514.1812800.677solid3LNby the metre40393910037845
18694800BZ
(N)HXCH FE180 E30-E60 4 x 2.5/2.5B2ca-s1a,d1,a1orange42.5/2.515.11283500.754solid3LNby the metre40393910037838
18694900BZ
(N)HXCH FE180 E30-E60 4 x 4/4B2ca-s1a,d1,a1orange44/416.72004640.87solid3LNby the metre40393910037821
18695000BZ
(N)HXCH FE180 E30-E60 4 x 6/6B2ca-s1a,d1,a1orange46/618.12976121.051solid3LNby the metre40393910037814
18695100BZ
(N)HXCH FE180 E30-E60 4 x 10/10B2ca-s1a,d1,a1orange410/1020.15048581.25solid3LNby the metre40393910037807
18698900BZ
(N)HXCH FE180 E30-E60 4 x 16/16B2ca-s1a,d1,a1orange416/1623.479612451.494stranded3LNby the metre40393910037487
18699000BZ
(N)HXCH FE180 E30-E60 4 x 25/16B2ca-s1a,d1,a1orange425/1627.2114217422.106stranded3LNby the metre40393910037470
18699100BZ
(N)HXCH FE180 E30-E60 4 x 35/16B2ca-s1a,d1,a1orange435/1629.8152621972.432stranded3LNby the metre40393910037463
18699200BZ
(N)HXCH FE180 E30-E60 4 x 50/25B2ca-s1a,d1,a1orange450/2534.8220330263.298stranded3LNby the metre40393910037456
18699300BZ
(N)HXCH FE180 E30-E60 4 x 70/35B2ca-s1a,d1,a1orange470/3539.5308241283.968stranded3LNby the metre40393910037449
18699400BZ
(N)HXCH FE180 E30-E60 4 x 95/50B2ca-s1a,d1,a1orange495/5045.2420854815.298stranded3LNby the metre40393910037432
18699500BZ
(N)HXCH FE180 E30-E60 4 x 120/70B2ca-s1a,d1,a1orange4120/7049.1538868636.051stranded3LNby the metre40393910037425
18699600BZ
(N)HXCH FE180 E30-E60 4 x 150/70B2ca-s1a,d1,a1orange4150/7054.3654083996.971stranded3LNby the metre40393910037418
18699700BZ
(N)HXCH FE180 E30-E60 4 x 185/95B2ca-s1a,d1,a1orange4185/9559.88159104709.075stranded3LNby the metre40393910037401
18699800BZ
(N)HXCH FE180 E30-E60 4 x 240/120B2ca-s1a,d1,a1orange4240/12067.9105461360011.41stranded3LNby the metre40393910037395
18724402BZ
(N)HXCH FE180 E30-E60 7 x 1.5/2.5B2ca-s1b,d1,a1orange71.5/2.516.11333900.884solid7Lby the metre40393910037227

Technical specifications

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E60* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V. Permitted operating temperature at conductor of +90˚C. Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
Circuit integrity FE 180
System circuit integrity E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Test voltage at 50Hz 4000
Nominal voltage 0.6/1kV
Minimum bending during installation (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (multi core) 12 x D
Minimum bending radius permanent (single core) 15 x D
Screened no
System Circuit Integrity is dependent on installation method.
For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Insulation Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Core colours CENELEC HD 308 S2, VDE 0293
Separator Plastic tape
Filler Flame retardant, halogen-free thermoplastic compound
Concentric conductor Bare copper wires with reinforced helix
Outer sheath material Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Outer sheath colour orange
Circuit integrity IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1
System circuit integrity DIN 4102-12, AREI-RGIE Section 4.3.3 FR2
Reaction to fire EN 13501-6
Euroclass B2ca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2

Documentation