JE-H(St)H...Bd FE180 E30-E90 fire alarm

Fire alarm cable, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Product variants & stock

Article No. Stock ProductOuter sheath colourNumber of coresOuter sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
188093
JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0.8 mmred25.61540.20.095by the metre40393910073164
188098
JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0.8 mmred26.32558.80.123by the metre40393910073126
188101
JE-H(St)H...Bd FE180 E30-E90 fire alarm 4x2x0.8 mmred2945100.40.21by the metre40393910073102
188103
JE-H(St)H...Bd FE180 E30-E90 fire alarm 8x2x0.8 mmred213.985223.70.52by the metre40393910073089
188105
JE-H(St)H...Bd FE180 E30-E90 fire alarm 12x2x0.8 mmred214.8126285.10.58by the metre40393910073065
188109
JE-H(St)H...Bd FE180 E30-E90 fire alarm 20x2x0.8 mmred218.8206428.10.80by the metre40393910073027
188107
JE-H(St)H...Bd FE180 E30-E90 fire alarm 16x2x0.8 mmred216.6166330.80.69by the metre40393910073041
188112
JE-H(St)H...Bd FE180 E30-E90 fire alarm 32x2x0.8 mmred2223265991.02by the metre40393910072990
188114
JE-H(St)H...Bd FE180 E30-E90 fire alarm 40x2x0.8 mmred225.5407771.51.38by the metre40393910072976
188116
JE-H(St)H...Bd FE180 E30-E90 fire alarm 52x2x0.8 mmred227.8529948.81.59by the metre40393910072952

Technical specifications

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V. Permitted operating temperature at conductor of +70˚C.
operating capacity, 1km @ 800Hz 120
Test voltage 50Hz, core/core 500
peak voltage 225
Capacitive coupling 0,8 mm, 100m @ 800Hz 200
Maximum loop resistance 0,8 mm 73.2
Minimum insulation resistance 100
Test voltage 50Hz, core/screen 2000
Circuit integrity FE 180
System circuit integrity E90
Installation temperature -5 °C - +50 °C
Operating temperature -30 °C - +70 °C
Minimum bending during installation (multi core) 7.5 x D
Minimum bending radius permanent (multi core) 7.5 x D
Minimal crush resistance / 10cm 1000 N
System Circuit Integrity is dependent on installation method.
Conductor Bare copper, solid, 0.8 mm diameter, VDE 0815
Insulation Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Core colours VDE 0815
Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
Outer sheath material Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
Circuit integrity IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020 (Rf 1 1/2), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1
System circuit integrity DIN 4102-12, AREI-RGIE Section 4.3.3 FR2
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2