Control cable flex, 300/500V, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
1 Conductor: stranded
2 Fire barrier: high-performance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC / LSZH






Product variants & stock
Download
Article No. | Stock | Product | Number of cores | Diameter mm² | Outer sheath diameter [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Construction | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|
188335 | FE180 flex 3 x 1.5 | 3 | 1.5 | 8.5 | 43 | 123 | 0.27 | LNPE | 40393910072419 | |
187554 | FE180 flex 5 x 1.5 | 5 | 1.5 | 10.3 | 72 | 182 | 0.40 | 3LNPE | 40393910073645 | |
187179 | FE180 flex 5 x 2.5 | 5 | 2.5 | 12.1 | 120 | 271 | 0.55 | 3LNPE | 40393910074505 | |
192367 | FE180 flex 7 x 1.5 | 7 | 1.5 | 11 | 101 | 222 | 0.44 | 6LPE | 40393910067620 | |
185228 | FE180 flex 8 x 1.5 | 8 | 1.5 | 12.4 | 115 | 273 | 0.56 | 6LNPE | 40393910077315 | |
191059 | FE180 flex 12 x 1.5 | 12 | 1.5 | 14 | 173 | 313 | 0.72 | 11LPE | 40393910070033 | |
191060 | FE180 flex 16 x 1.5 | 16 | 1.5 | 16 | 231 | 410 | 0.89 | 15LPE | 40393910070026 | |
191061 | FE180 flex 21 x 1.5 | 21 | 1.5 | 18 | 303 | 527 | 1.10 | 20LPE | 40393910070019 |
Technical specifications
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) | 4 x D |
---|---|
Minimum bending during installation (multi core) | 6 x D |
Circuit integrity | FE 180 |
---|---|
Installation temperature | -5 °C - +50 °C |
Operating temperature | -45 °C - +90 °C |
Test voltage at 50Hz | 2000 |
---|---|
Nominal voltage | 300/500V |
Additional dimensions available on request. |
Conductor | Bare copper, stranded, IEC 60228 class 5, EN 60228 |
---|---|
Insulation | Special compound, HD 604 S1 part 5 H |
Core colours | CENELEC HD 308 S2 |
Filler | HD 604 S1 part 5 H |
Outer sheath material | Compound, HD 604 S1 part 5 H |
Circuit integrity | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
---|---|
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD, SEV TP 20B/3C 3.4.3 |
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA, SEV TPV11 |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1, SEV TP 20B/3C 3.4.1.1 |
Flame spread | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Section 4.3.3 F2, SEV TP 20B/3C 3.4.1.3 |