1 Conductor: solid or stranded
2 Insulation: fire resistant special compound
3 Drain wire: tinned copper
4 Inner covering: glass fibre tape
5 Shielding: Alu-laminated tape
6 Inner sheath: Polyolefin compound
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LSZH
Product variants & stock
Article No.
Stock
Product
Outer sheath colour
Diameter mm²
Outer sheath diameter [mm]
CU rate [kg/km]
Weight [kg/km]
Fire load [kWh/m]
GTIN / EAN
194031
Armoured Standard Fire Safety Cable
red
1.5
11.5
48
184
0.40
40393910064834
Technical specifications
Armoured cable for fire alarm systems and emergency lighting for permament installation in buildings.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core)
6 x D
Minimum bending during installation (multi core)
6 x D
Test voltage at 50Hz
2000
Nominal voltage
300/500V
Additional dimensions available on request.
Conductor
Bare copper, solid or stranded in accordance with IEC 60228 and EN 60228