DCS trunk cable MTP, 12-144 fibres OS2

for interconnecting DCS modules

DCS trunk cable MTP, 12-144 fibres OS2

Product variants & stock

Article No. Stock ProductOuter sheath colourNumber of fibresOuter sheath diameter [mm]Minimum bending radiusTensile load short term [N]Tensile load continuous [N]Crush resistance short term [N]Crush resistance continuous [N]PolarityNumber of connectors side ANumber of connectors side BNumber of fibres per connector ANumber of fibres per connector BWeight [kg]Packing unitGTIN / EAN
474040
DCS trunk cable 1x MTP - 1x MTPyellow125.91203000100040001200A1112120.3 kgby the metre40393910144161
474041
DCS trunk cable 2x MTP - 2x MTPyellow249.92008000410040001200A2212120.3 kgby the metre40393910144154
474042
DCS trunk cable 4x MTP - 4x MTPyellow489.92008000410040001200A4412120.3 kgby the metre40393910144147
474043
DCS trunk cable 6x MTP - 6x MTPyellow7210.72158000410040001200A6612120.3 kgby the metre40393910144130
474044
DCS trunk cable 8x MTP - 8x MTPyellow9612.92558000410040001200A8812120.3 kgby the metre40393910144123
474045
DCS trunk cable 12x MTP - 12x MTPyellow14415.83208000410040001200A121212120.3 kgby the metre40393910144116
474050
DCS trunk cable 1x MTP - 1x MTPyellow125.91203000100040001200C1112120.3 kgby the metre40393910144109
474051
DCS trunk cable 2x MTP - 2x MTPyellow249.92008000410040001200C2212120.3 kgby the metre40393910144093
474052
DCS trunk cable 4x MTP - 4x MTPyellow489.92008000410040001200C4412120.3 kgby the metre40393910144086
474053
DCS trunk cable 6x MTP - 6x MTPyellow7210.72158000410040001200C6612120.3 kgby the metre40393910144079
474054
DCS trunk cable 8x MTP - 8x MTPyellow9612.92558000410040001200C8812120.3 kgby the metre40393910144062
474055
DCS trunk cable 12x MTP - 12x MTPyellow14415.83208000410040001200C121212120.3 kgby the metre40393910144055

Technical specifications

Compact, metal-free cable construction with FR/LS0H cable sheath and 12 to 144 fibres.
OS2 versions with Euroclass Dca are available (Euroclass Cca or B2ca version available on request).
Sticker labelling at both cable ends.
The length of individual cables ("legs") may be defined on the basis of a specific project (standard 0.75 m).
The leg separation is effected with a divider housing.
All individual cables are assembled using MTP® connectors with high-performance 12-fibre Elite® ferrules (MTP8/MTP24 available on request).
Standard connectivity methods can be type A or type C (other types available on request).
The cables are fitted at both ends with protective sleeves.
DCS trunk cable (FR/LS0H) with 12-144 fibres OS2.
High-performance connector assembly at either end with MTP Elite (male).
Sticker labelling at both cable ends.
Housing colour connector A yellow
Housing colour connector B yellow
OS2 MTP-on-MTP trunk cables are suitable for all high-performance applications with duplex and parallel optic signals in a data centre environment.
They are particularly used when installation requires sturdy, metal-free indoor cables that provide enhanced crush resistance and rodent protection.
For duplex applications, the pre-assempled connectors at either end of the cable are connected to the DCS modules.
The DCS trunk cables are assembled to a very high quality and guarantee optimum values for optical performance (IL/RL).
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24
MTP standard (IEC) IEC 61754-7, IEC 61755-3-31, IEC 61755-3-32
Polarity standard TIA-568-C.3 Type A,B,C
Outer sheath material FR/LSZH
Outer sheath colour yellow
Fibre type E9/125 G.652.D BLO
Colour code IEC 60304
Connector type side A MTP
Connector gender side A male
Ferrule polishing connector A Elite APC 8°
IL maximal, connector A 0.3 dB
IL typical, connector A 0.1 dB
RL minimal, connector A 65 dB
RL typical, connector A 70 dB
Connector type side B MTP
Connector gender side B male
Ferrule polishing connector B Elite APC 8°
IL maximal, connector B 0.3 dB
IL typical, connector B 0.1 dB
RL minimal, connector B 65 dB
RL typical, connector B 70 dB

Documentation