DCS breakout cable, MTP - MTP, G50/125 OM3

for interconnecting DCS modules

DCS breakout cable MTP, 12-144 fibres OM3

Product variants & stock

Article No. Stock ProductNumber of fibresOuter sheath diameter [mm]Tube diameter [mm]PolarityNumber of connectors side ANumber of connectors side BGradationPacking unitGTIN / EAN
475060
DCS breakout cable 1x MTP - 1x MTP124.52A11by the metre40393910143430
475061
DCS breakout cable 2x MTP - 2x MTP246.62A22equal lengthby the metre40393910143423
475062
DCS breakout cable 4x MTP - 4x MTP486.62A44equal lengthby the metre40393910143416
475063
DCS breakout cable 6x MTP - 6x MTP727.82A66graduated lengthby the metre40393910143409
475064
DCS breakout cable 8x MTP - 8x MTP969.22A88graduated lengthby the metre40393910143393
475065
DCS breakout cable 12x MTP - 12x MTP14412.52A1212graduated lengthby the metre40393910143386
475070
DCS breakout cable 1x MTP - 1x MTP124.52C11by the metre40393910143379
475071
DCS breakout cable 2x MTP - 2x MTP246.62C22equal lengthby the metre40393910143362
475072
DCS breakout cable 4x MTP - 4x MTP486.62C44equal lengthby the metre40393910143355
475073
DCS breakout cable 6x MTP - 6x MTP727.82C66graduated lengthby the metre40393910143348
475074
DCS breakout cable 8x MTP - 8x MTP969.22C88graduated lengthby the metre40393910143331
475075
DCS breakout cable 12x MTP - 12x MTP14412.52C1212graduated lengthby the metre40393910143324

Technical specifications

Compact, metal-free cable construction with FR/LS0H cable sheath and 12 to 144 fibres.
Sticker labelling at both cable ends.
The length of individual cables ("legs") may be defined on the basis of a specific project (standard 0.75 m).
All individual cables are assembled using MTP® connectors with high-performance 12-fibre Elite® ferrules (MTP8/MTP24 available on request).
Standard connectivity methods can be type A or type C (other types available on request).
The cables are fitted at both ends with protective sleeves.
Cable raw material FO Indoor M-BO / J-F(ZN)HH, Eca
DCS breakout cable (FR/LS0H) with 12-144 fibres OM3.
High-performance connector assembly at either end with MTP Elite (male).
Sticker labelling at both cable ends.
Insertion Loss (IL) is determined by the latest measurement methods under EFL multimode excitation conditions (EFL = Encircled Flux Launch) at 850 nm in accordance with IEC 61280-4-1.
MTP breakout cables are suitable for all high-performance applications with duplex and parallel optic signals in a data centre environment.
They are particularly used when installation requires sturdy, metal-free indoor cables that provide enhanced crush resistance.
For duplex applications, the pre-assempled connectors at either end of the cable are connected to the DCS modules.
The DCS breakout cables are assembled to a very high quality and guarantee optimum values for optical performance (IL/RL).
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24
MTP standard (IEC) IEC 61754-7, IEC 61755-3-31, IEC 61755-3-32
Polarity standard TIA-568-C.3 Type A,B,C
Outer sheath material FR/LSZH
Outer sheath colour turquoise
Housing colour connector A aqua
Housing colour connector B aqua
Fibre type G50/125 OM3
Colour code IEC 60304
Connector type side A MTP
Connector gender side A male
Ferrule polishing connector A Elite PC 0°
IL maximal, connector A 0.25 dB
IL typical, connector A 0.15 dB
RL minimal, connector A 35 dB
RL typical, connector A 45 dB
Connector type side B MTP
Connector gender side B male
Ferrule polishing connector B Elite PC 0°
IL maximal, connector B 0.25 dB
IL typical, connector B 0.15 dB
RL minimal, connector B 35 dB
RL typical, connector B 45 dB

Documentation