CU 7002 6x4P Breakout Light (BOL)

Data cable, S/FTP, Category 7, AWG23, Euroclass Dca
1000 MHz

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.4 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Single cable sheath: FRNC/LS0H orange RAL 2003
6 Outer foil of Breakout Light (BOL) construction:
Polyester foil, transparent, sealed

01_RoHS 04_Propagation 05_Spread- 02_PoEp_rt 10_Schielded_EN 06_Density 08_System- 03_LS0H CPR_Dca CPR_Eca CPR_Fca

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
18848600DZ
CU 7002 6x4P BOLDca-s2,d1,a16 x (4 x 2 x 0.57 (AWG23))21.8186.63860.96by the metre40393910034516

Technical specifications

Electrically and mechanically superior quality Cat.7 data cable - exceeds the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-4-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Easy handling, small outer diameter and reduced weight thanks to the Breakout Light construction with outer polyester foil instead of an overall cable sheath.
Considerable shorter installation time due to the multi-cable construction.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Tensile strength (4P) 600 N
Minimum bending radius (during installation) 170 mm
Minimal crush resistance / 10cm 1000 N
Minimum number of impacts 10
AWG 23
Solid / Flex Solid wire
Minimum bending radius (permanently installed) 85 mm
Data cable for structured premises cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all applications up to class F applications (600 MHz) in accordance with EN 50173-1 and ISO/IEC 11801 and for the transmission of broadband signals (such as cable TV) in accordance with IEC 15018.
Applicable for Power over Ethernet (PoE) / PoE+ and 4PPoE up to 100W.
Especially suitable for Consolidation Points (e.g. in open-plan offices).
Category Cat.7
GBit/s Up to 10 Gbit/s
Loop resistance at 20 °C 140 Ω/km
Operating capacity 42 pF/m
Impedance at 100 MHz, ±5Ω 100 Ω
NVP % 81
Delay skew 12 ns/100 m
Shielding shielded
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
Transfer impedance 1/10/30 MHz < 6/6/10 mΩ/m
Coupling attenuation 85 dB
Segregation class d
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Field of application Indoor
Reaction to fire EN 13501-6
Euroclass Dca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Cables standard ISO/IEC 61156-5, EN 50288-4-1
Cat./Class Cat.7 / Class F
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH
Outer sheath colour orange

Documentation