CU 692 4P

Data cable, U/UTP, Category 6A, AWG23, Euroclass Dca
650 MHz

1 Inner conductor: bare copper wire
2 PE insulated conductor: 1.1 mm ∅ PE
3 Pair seperator
4 Outer sheath: FRNC/LS0H

01_RoHS 04_Propagation 05_Spread- 02_PoE 06_Density 08_System- 03_LS0H CPR_Dca CPR_Eca

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath dimensions [mm]CU rate [kg/km]Weight [kg]Packing unitGTIN / EAN
19462600DL
CU 692 4PDca-s2,d1,a14 x 2 x 0.57 (AWG23)7.921.640.06 kg500 m drum40393910021349

Technical specifications

Electrically and mechanically high-quality Cat.6A data cable - fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-11-1. Robust cable design with reliable electrical performance thanks to stabilising element. Provides a large amount of spare capacity at the NEXT and Alien NEXT limit values due to cable construction with a pair separator (cross) and improved sheath design. Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Tensile strength (4P) 91 N
Minimum bending radius (during installation) 66 mm
Minimal crush resistance / 10cm 1000 N
Minimum number of impacts 3
AWG 23
Solid / Flex Solid wire
Minimum bending radius (permanently installed) 33 mm
Data cable for structured premesis cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class EA applications (500 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.
Category Cat.6A
GBit/s Up to 10 Gbit/s
Loop resistance at 20 °C 136 Ω/km
Operating capacity 55 pF/m
Impedance at 100 MHz, ±5Ω 100 Ω
NVP % 66
Delay skew 30 ns/100 m
Shielding unshielded
TCL 50 dB
Segregation class b
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Wire colour white/blue-white, white/orange-white, white/green-white, white/brown-white (with length stripes)
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Field of application Indoor
Reaction to fire EN 13501-6
Euroclass Dca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2 (FRNC/LS0H)
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Cables standard ISO/IEC 61156-5, EN 50288-11-1
Cat./Class Cat.6A / Class EA
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH
Outer sheath colour orange

Documentation