CU 6552 4P / 2x4P F8
Data cable, F/FTP, Category 6A, AWG 23, Euroclass Cca
500 MHz
1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.3 mm Ø
3 Screen (pair): Alu PETP foil
4 Drain wire: Tinned copper wire
5 Overall screen: Alu PETP foil
6 Outer sheath: FRNC/LS0H orange or white











Product variants & stock
Download
Article No. | Stock | Product | Reaction to fire | Dimensions n x p x [mm (AWG)] | Outer sheath dimensions [mm] | CU rate [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Packing unit | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|
19145400CK | CU 6552 4P | Cca-s1a,d1,a1 | 4 x 2 x 0.55 (AWG23) | 7 | 20.0 | 49 | 0.14 | 1000 m drum | 40393910030846 | |
19145600CL | CU 6552 2x4P | Cca-s1,d1,a1 | 2 x (4 x 2 x 0.55 (AWG23)) | 7.0 x 14.3 | 40.0 | 98 | 0.28 | 500 m drum | 40393910030679 |
Technical specifications
Electrically and mechanically improved quality Cat.6A data cable - fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and prEN 50288-10-1.
Excellent shielding effect due to individually screened pairs and overall foil screen.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Excellent shielding effect due to individually screened pairs and overall foil screen.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Tensile strength (4P) | 95 N |
---|---|
Tensile strength (2x4P) | 190 N |
Minimum bending radius (during installation) | 56 mm |
Minimal crush resistance / 10cm | 1000 N |
Minimum number of impacts | 10 |
AWG | 23 |
Solid / Flex | Solid wire |
Minimum bending radius (permanently installed) | 28 mm |
Data cable for structured premises cabling. For the transmission of digital and analogue voice, video and data signals. Suitable for all ICT network applications up to class EA applications (500 MHz) in accordance with EN 50173-1 and ISO/IEC 11801. Applicable for Power over Ethernet (PoE) / PoE+. |
Category | Cat.6A |
---|---|
GBit/s | Up to 10 Gbit/s |
Loop resistance at 20 °C | 150 Ω/km |
Operating capacity | 42 pF/m |
Impedance at 100 MHz, ±5Ω | 100 Ω |
NVP % | 79 |
Delay skew | 5 ns/100 m |
Shielding | shielded |
Near end unbalance attenuation LCL at 1-600 MHz | 40 dB |
Transfer impedance 1/10/30 MHz | < 50/100/200 mΩ/m |
Coupling attenuation | 70 dB |
Segregation class | c |
Installation temperature | 0 °C - +50 °C |
---|---|
Operating temperature | -20 °C - +60 °C |
Wire colour | white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708 |
Imprint | DATWYLER «cable type» «additional text» «batch number» «meter marks» |
Field of application | Indoor |
Reaction to fire | EN 13501-6 |
---|---|
Euroclass | Cca |
Smoke density | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD |
Zero halogen no corrosive gases | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA |
Flame propagation | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1 |
Flame spread | IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2 |
Cables standard | ISO/IEC 61156-5, EN 50288-10-1 |
Cat./Class | Cat.6A / Class EA |
PoE | IEEE 802.3bt Type 4 (100W) |
Outer sheath material | FRNC/LSZH |
---|---|
Outer sheath colour | orange |
Documentation
-
GHMT Type Approval Certificate
Download PDF [ 240.8 KB ]
-
GHMT Type Approval Certificate
Download PDF [ 246.052 KB ]
-
Datasheet
Download PDF [ 167.508 KB ]
-
Datasheet
Download PDF [ 168.891 KB ]
-
Datasheet
Download PDF [ 168.786 KB ]
-
Datasheet
Download PDF [ 168.209 KB ]
-
Datasheet
Download PDF [ 167.982 KB ]
-
Datasheet
Download PDF [ 168.074 KB ]
-
Tender text
Download UNKNOWN [ 64.667 KB ]