CU 6502 4P SHF1

Data cable, U/FTP, Category 6A, AWG23, Euroclass Dca
500 MHz

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.3 mm Ø
3 Screen (pair): Alu PETP foil
4 Drain wire: Tinned copper wire
5 Outer sheath: FRNC/LS0H SHF1

01_RoHS 04_Propagation 05_Spread- 02_PoE 10_Schielded_EN 06_Density 08_System- 03_LS0H CPR_Dca CPR_Eca

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
19439202DK
CU 6502 4P U/FTP CAT6A SHF1 GRDca-s2,d2,a14 x 2 x 0.55 (AWG23)7.220.0530.1781000 m drum40393910022278

Technical specifications

Electrically and mechanically improved quality Cat.6A data cable - fulfils the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and prEN 50288-10-1. Good shielding effect due to individually screened pairs. Oil resistant, fire retardant and halogen free sheath. Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801. Certified by Det Norske Veritas.
AWG 23
Tensile strength (4P) 95 N
Tensile strength (2x4P) 190 N
Minimum bending radius during installation 56 mm
Minimum bending radius permanently installed 28 mm
Minimal crush resistance / 10cm 1000 N
Minimum number of impacts 10
Solid / Flex Solid wire
Segregation class c
Category Cat.6A
Loop resistance at 20 °C 150 Ω/km
Operating capacity 42 pF/m
Delay skew 5 ns/100 m
Impedance at 100 MHz, ±5Ω 100 Ω
Transfer impedance 1/10/30 MHz < 50/100/200 mΩ/m
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
NVP % 79
Coupling attenuation 55 dB
GBit/s Up to 10 Gbit/s
Shielding shielded
Data cable for structured premises cabling - designed for use in industrial areas, particularly for higher requirements in offshore and marine applications.
Oil resistant, flame retardant and zero halogen outer sheath.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class EA applications (500 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.
Supported Applications: 10Base-T, 100Base-T, 1000Base-T, 2.5GBase-T, 5GBase-T, 10GBase-T, Fieldbus
Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
Field of application Off-Shore and Shipbuilding
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Reaction to fire EN 13501-6
Euroclass Dca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Cables standard ISO/IEC 61156-5, EN 50288-10-1
Cat./Class Cat.6A / Class EA
DNV standard DNVGL-CP-0403
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH SHF1
Outer sheath colour grey