FE5-CL

Safety cable, 0.6/1kV, armoured with rodent protection, euroclass B2ca
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5. H

1 Conductor: solid/stranded
2 Insulation: cross-linked PE, zero halogen
3 Inner sheath: Polyolefin, flame retardant, zero halogen
4 Armouring: galvanised steel tape
5 Sheath: FRNC/LSZH

07_Circuit- 04_Propagation 05_Spread 06_Density 08_System- 03_LS0H CPR_B2ca CPR_Cca CPR_Dca CPR_Eca CPR_Fca

Product variants & stock

Article No. Stock ProductReaction to fireDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionPacking unitGTIN / EAN
18838900BZ
FE5-CL-J 5 x 10B2ca-s1a,d1,a110184807321.56solid3LNPEby the metre40393910035162
19040100BZ
FE5-CL-J 5 x 16B2ca-s1a,d1,a1162476811202.03stranded3LNPEby the metre40393910032888
18092900BZ
FE5-CL-J 7 x 6B2ca-s1a,d1,a16174036241.1solid6LPEby the metre40393910042597
18453100BZ
FE5-CL-J 7 x 10B2ca-s1a,d1,a110206729501.48solid6LPEby the metre40393910040128
19059500BZ
FE5-CL-J 5 x 6B2ca-s1a,d1,a16162884900.92solid3LNPEby the metre40393910032604
19103600BZ
FE5-CL-J 5 x 50B2ca-s1a,d1,a15036240031444.74stranded3LNPEby the metre40393910032079
19106300BZ
FE5-CL-J 5 x 25B2ca-s1a,d1,a12528120017102.76stranded3LNPEby the metre40393910031997
19106400BZ
FE5-CL-J 5 x 2.5B2ca-s1a,d1,a12.5121202600.59solid3LNPEby the metre40393910031942
19109000BZ
FE5-CL-J 5 x 35B2ca-s1a,d1,a13531.8168022773.44stranded3LNPEby the metre40393910031867
19156800BZ
FE5-CL-J 3 x 10B2ca-s1a,d1,a110162884990.91solidLNPEby the metre40393910030372
19160000BZ
FE5-CL-J 5 x 95B2ca-s1a,d1,a19549456058548.16stranded3LNPEby the metre40393910030280
19273000BZ
FE5-CL-J 3 x 2.5B2ca-s1a,d1,a12.510721680.41solidLNPEby the metre40393910026900
19273100BZ
FE5-CL-J 5 x 4B2ca-s1a,d1,a14141923640.73solid3LNPEby the metre40393910026870
19626800BZ
FE5-CL-J 3 x 1.5B2ca-s1a,d1,a11.59431180.3solidLNPEby the metre40393910018424
19626400BZ
FE5-CL-J 5 x 1.5B2ca-s1a,d1,a11.510721750.45solid3LNPEby the metre40393910018455
19109100BZ
FE5-CL-J 3 x 4B2ca-s1a,d1,a14111152380.48solidLNPEby the metre40393910031812
19164500BZ
FE5-CL-J 3 x 6B2ca-s1a,d1,a16131733290.65solidLNPEby the metre40393910030181
19586400BZ
FE5-CL-O 2 x 2.5B2ca-s1a,d1,a12.510491510.37solidLNby the metre40393910021134
19167200BZ
FE5-CL-J 4 x 1.5B2ca-s1a,d1,a11.59581510.36solid3LPEby the metre40393910030037

Technical specifications

For permanent installation in dry, damp or wet areas, on or behind plasterwork or in walls or concrete. Also suitable for outdoor applications. The cable should only be laid directly in earth or water if a protective conduit is used. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 12 x D
Minimum bending during installation (single core) 15 x D
Minimum bending radius permanent (single core) 15 x D
Minimum bending during installation (multi core) 12 x D
Circuit integrity (FE180) No
System circuit integrity No
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Additional dimensions available on request.
Conductor Bare copper, solid or stranded in accordance with IEC 60228 and EN 60228
Insulation Cross-linked Polyethylene CENELEC HD 604 S1 part 5 sec. H
Core colours CENELEC HD 308 S2
Armouring (rodent protection) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Outer sheath material Flame retardant Polyolefin compound CENELEC HD 604 S1 part 5 sec. H
Reaction to fire EN 13501-6
Euroclass B2ca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2

Documentation