Back to: Safety cables

FE180 E30 CL

Safety cable, 0.6/1kV, armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H

1 Conductor: solid / stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner Sheath: Polyolefin flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH

Description

Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.

  • Conductor Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
  • Insulation Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
  • Core colours CENELEC HD 308 S2
  • Filler HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
  • Inner sheath Compound, HD 604 S1 part 5 H(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 ""HM 4"", flame-retardant)
  • Outer sheath material Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)
  • Armouring (rodent protection) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
  • Test voltage at 50Hz 3500 V
  • Installation temperature -5 °C - +50 °C
  • Operating temperature -45 °C - +90 °C
  • Circuit Integrity E30
  • Insulation integrity FE 180
  • Minimum bending during installation (multi core) 12 x D
  • Minimum bending during installation (single core) 15 x D
  • Minimum bending radius permanent (multi core) 12 x D
  • Minimum bending radius permanent (single core) 15 x D
  • * System Circuit Integrity is dependent on installation method
  • Insulation Integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
  • System circuit integrity DIN 4102-12, AREI-RGIE Art.104-FR2
  • Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD, SEV TP 20B/3C 3.4.3
  • Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA, SEV TPV11
  • Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1, SEV TP 20B/3C 3.4.1.1
  • Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Art.104-F2, SEV TP 20B/3C 3.4.1.3

Documentation

EN DE NL FR CN ES IT
Datasheet Datasheet Datasheet Datasheet Datasheet file-icon Datasheet Datasheet

Versions

Article No. Stock Product Number of CoresDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorGTIN / EAN
193886 FE180 E30 CL 3 1.5 11 43 210 0.46 kWh/msolid 40393910065367
187199 FE180 E30 CL 3 2.5 12 72 255 0.50 kWh/msolid 40393910074345
191097 FE180 E30 CL 3 4 14 115 373 0.69 kWh/msolid 40393910069785
191121 FE180 E30 CL 3 6 15.8 173 481 0.90 kWh/msolid 40393910069648
188354 FE180 E30 CL 3 10 18 288 651 1.20 kWh/msolid 40393910072303
191595 FE180 E30 CL 4 2.5 14 96 296 0.56 kWh/msolid 40393910069143
187167 FE180 E30 CL 4 4 16 154 408 0.79 kWh/msolid 40393910074512
188352 FE180 E30 CL 4 6 17 230 535 1.06 kWh/msolid 40393910072327
191038 FE180 E30 CL 5 2.5 14 120 388 0.76 kWh/msolid 40393910070040
188350 FE180 E30 CL 5 4 16 192 488 1.05 kWh/msolid 40393910072341
188353 FE180 E30 CL 5 6 17.5 288 640 1.28 kWh/msolid 40393910072310
188397 FE180 E30 CL 5 10 21 480 964 1.76 kWh/msolid 40393910072082
187197 FE180 E30 CL 7 2.5 16 168 476 0.91 kWh/msolid 40393910074369
188355 FE180 E30 CL 7 6 19 403 794 1.53 kWh/msolid 40393910072297
188356 FE180 E30 CL 7 10 23 672 1201 2.13 kWh/msolid 40393910072280
192461 FE180 E30 CL 8 1.5 15 115 403 0.85 kWh/msolid 40393910067477
187128 FE180 E30 CL 8 2.5 16 192 489 1.04 kWh/msolid 40393910074642
191104 FE180 E30 CL 8 4 18 308 684 1.36 kWh/msolid 40393910069754
Additional dimensions available on request