DCS trunk cable MTP, 12-144 fibres OS2

for interconnecting DCS modules

DCS trunk cable MTP, 12-144 fibres OS2

Product variants & stock

Article No. Stock ProductOuter sheath colourNumber of fibresOuter sheath diameter [mm]Minimum bending radiusTensile load short term [N]Tensile load continuous [N]Crush resistance short term [N]Crush resistance continuous [N]PolarityNumber of connectors side ANumber of connectors side BNumber of fibres per connector ANumber of fibres per connector BWeight [kg]Packing unitGTIN / EAN
474040
DCS trunk cable 1x MTP - 1x MTPyellow125.91203000100040001200A1112120.3 kgby the metre40393910144161
474041
DCS trunk cable 2x MTP - 2x MTPyellow249.92008000410040001200A2212120.3 kgby the metre40393910144154
474042
DCS trunk cable 4x MTP - 4x MTPyellow489.92008000410040001200A4412120.3 kgby the metre40393910144147
474043
DCS trunk cable 6x MTP - 6x MTPyellow7210.72158000410040001200A6612120.3 kgby the metre40393910144130
474044
DCS trunk cable 8x MTP - 8x MTPyellow9612.92558000410040001200A8812120.3 kgby the metre40393910144123
474045
DCS trunk cable 12x MTP - 12x MTPyellow14415.83208000410040001200A121212120.3 kgby the metre40393910144116
474050
DCS trunk cable 1x MTP - 1x MTPyellow125.91203000100040001200C1112120.3 kgby the metre40393910144109
474051
DCS trunk cable 2x MTP - 2x MTPyellow249.92008000410040001200C2212120.3 kgby the metre40393910144093
474052
DCS trunk cable 4x MTP - 4x MTPyellow489.92008000410040001200C4412120.3 kgby the metre40393910144086
474053
DCS trunk cable 6x MTP - 6x MTPyellow7210.72158000410040001200C6612120.3 kgby the metre40393910144079
474054
DCS trunk cable 8x MTP - 8x MTPyellow9612.92558000410040001200C8812120.3 kgby the metre40393910144062
474055
DCS trunk cable 12x MTP - 12x MTPyellow14415.83208000410040001200C121212120.3 kgby the metre40393910144055

Technical specifications

Compact, metal-free cable construction with FR/LS0H cable sheath and 12 to 144 fibres. OS2 versions with Euroclass D<sub>ca</sub> are available (Euroclass C<sub>ca</sub> or B2<sub>ca</sub> version available on request). Sticker labelling at both cable ends. The length of individual cables (&quot;legs&quot;) may be defined on the basis of a specific project (standard 0.75 m). The leg separation is effected with a divider housing. All individual cables are assembled using MTP<sup>®</sup> connectors with high-performance 12-fibre Elite<sup>®</sup> ferrules (MTP<sub>8</sub>/MTP<sub>24</sub> available on request). Standard connectivity methods can be type A or type C (other types available on request). The cables are fitted at both ends with protective sleeves.
DCS trunk cable (FR/LS0H) with 12-144 fibres OS2.
High-performance connector assembly at either end with MTP Elite (male).
Sticker labelling at both cable ends.
OS2 MTP-on-MTP trunk cables are suitable for all high-performance applications with duplex and parallel optic signals in a data centre environment.
They are particularly used when installation requires sturdy, metal-free indoor cables that provide enhanced crush resistance and rodent protection.
For duplex applications, the pre-assempled connectors at either end of the cable are connected to the DCS modules.
The DCS trunk cables are assembled to a very high quality and guarantee optimum values for optical performance (IL/RL).
Housing colour connector A yellow
Housing colour connector B yellow
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24
MTP standard (IEC) IEC 61754-7, IEC 61755-3-31, IEC 61755-3-32
Polarity standard TIA-568-C.3 Type A,B,C
Outer sheath material FR/LSZH
Outer sheath colour yellow
Fibre type E9/125 G.652.D BLO
Colour code IEC 60304
Connector type side A MTP
Connector gender side A male
Ferrule polishing connector A Elite APC 8°
IL maximal, connector A 0.3 dB
IL typical, connector A 0.1 dB
RL minimal, connector A 65 dB
RL typical, connector A 70 dB
Connector type side B MTP
Connector gender side B male
Ferrule polishing connector B Elite APC 8°
IL maximal, connector B 0.3 dB
IL typical, connector B 0.1 dB
RL minimal, connector B 65 dB
RL typical, connector B 70 dB

Documentation