Safety cable, 0.6/1kV, Keram
Halogen-free, with improved fire characteristics;
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
System Circuit Integrity is provided up to 400 V operating voltage.
Permitted operating temperature at conductor of +90˚C.
Radio de flexión mínimo permanente (multinúcleo)
12 x D
Plegado mínimo durante la instalación (núcleo único)
15 x D
Radio de flexión mínimo permanente (núcleo único)
15 x D
Mínimo de flexión durante la instalación (multinúcleo)
12 x D
Observaciones radio de flexión
50% reduction if installation at 30°C and with a template
Integridad del aislamiento
FE 180
Integridad de circuito
E30-E60*
Temperatura de instalación
-5 °C - +50 °C
Temperatura de funcionamiento
-45 °C - +90 °C
Tensión de prueba a 50 Hz
3500
Tensión nominal
0.6/1kV
* System Circuit Integrity is dependent on installation method
Conductor
Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Aislamiento
Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Colores principales
CENELEC HD 308 S2(≥16 mm2: CENELEC HD 308 S2, VDE 0293)
Relleno
HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Material exterior de la vaina
Compound, HD 604 S1 part 5 H(16 mm2: polyolefin compound in accordance with VDE 0276-604, CENELEC HD 604 S1 "HM4", flame-retardant)