(N)HXCH FE180 E30-E60 B2ca

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Reacción al fuego según EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

07_Circuit 08_System 05_Spread 06_Density 03_LS0H 04_Propagation

Variantes de productos y existencias

Artículo No. Stock ProdottoReacción al fuegoColor de la funda exteriorDiámetro [mm2]Diámetro exterior de la vaina [mm]Prop. CU [kg/km]Peso [kg/km]Carga de fuego [kWh/m]ConductorConstrucciónUnidad de embalajeGTIN / EAN
18694300BZ
(N)HXCH FE180 E30-E60 2 x 1.5/1.5B2ca-s1a,d1,a1anaranjado1.5/1.512.7522210.551de corridoLNpor metro40393910037883
18694400BZ
(N)HXCH FE180 E30-E60 2 x 2.5/2.5B2ca-s1a,d1,a1anaranjado2.5/2.513.5802690.612de corridoLNpor metro40393910037876
18723200BZ
(N)HXCH FE180 E30-E60 2 x 4/4B2ca-s1a,d1,a1anaranjado4/414.91233500.706de corridoLNpor metro40393910037296
18723400BZ
(N)HXCH FE180 E30-E60 2 x 6/6B2ca-s1a,d1,a1anaranjado6/6161824280.79de corridoLNpor metro40393910037289
18694500BZ
(N)HXCH FE180 E30-E60 3 x 1.5/1.5B2ca-s1a,d1,a1anaranjado1.5/1.513.2662460.599de corrido3Lpor metro40393910037869
18694600BZ
(N)HXCH FE180 E30-E60 3 x 2.5/2.5B2ca-s1a,d1,a1anaranjado2.5/2.514.11043030.784de corrido3Lpor metro40393910037852
18723800BZ
(N)HXCH FE180 E30-E60 3 x 16/16B2ca-s1a,d1,a1anaranjado16/1621.3624.710271.348trenzado3Lpor metro40393910037272
18723900BZ
(N)HXCH FE180 E30-E60 3 x 25/16B2ca-s1a,d1,a1anaranjado25/162590214331.799trenzado3Lpor metro40393910037265
18724000BZ
(N)HXCH FE180 E30-E60 3 x 35/16B2ca-s1a,d1,a1anaranjado35/1637.3119017992.096trenzado3Lpor metro40393910037258
18724100BZ
(N)HXCH FE180 E30-E60 3 x 50/25B2ca-s1a,d1,a1anaranjado50/2531.7172324502.689trenzado3Lpor metro40393910037241
18724200BZ
(N)HXCH FE180 E30-E60 3 x 70/35B2ca-s1a,d1,a1anaranjado70/3536241033423.32trenzado3Lpor metro40393910037234
18698500BZ
(N)HXCH FE180 E30-E60 3 x 95/50B2ca-s1a,d1,a1anaranjado95/5041.1329644454.416trenzado3Lpor metro40393910037524
18698600BZ
(N)HXCH FE180 E30-E60 3 x 120/70B2ca-s1a,d1,a1anaranjado120/7044.5423655245.002trenzado3Lpor metro40393910037517
18698700BZ
(N)HXCH FE180 E30-E60 3 x 150/70B2ca-s1a,d1,a1anaranjado150/7049.2510067306.114trenzado3Lpor metro40393910037500
18698800BZ
(N)HXCH FE180 E30-E60 3 x 240/120B2ca-s1a,d1,a1anaranjado240/12061.58242109089.391trenzado3Lpor metro40393910037494
18694700BZ
(N)HXCH FE180 E30-E60 4 x 1.5/1.5B2ca-s1a,d1,a1anaranjado1.5/1.514.1812800.677de corrido3LNpor metro40393910037845
18694800BZ
(N)HXCH FE180 E30-E60 4 x 2.5/2.5B2ca-s1a,d1,a1anaranjado2.5/2.515.11283500.754de corrido3LNpor metro40393910037838
18694900BZ
(N)HXCH FE180 E30-E60 4 x 4/4B2ca-s1a,d1,a1anaranjado4/416.72004640.87de corrido3LNpor metro40393910037821
18695000BZ
(N)HXCH FE180 E30-E60 4 x 6/6B2ca-s1a,d1,a1anaranjado6/618.12976121.051de corrido3LNpor metro40393910037814
18695100BZ
(N)HXCH FE180 E30-E60 4 x 10/10B2ca-s1a,d1,a1anaranjado10/1020.15048581.25de corrido3LNpor metro40393910037807
18698900BZ
(N)HXCH FE180 E30-E60 4 x 16/16B2ca-s1a,d1,a1anaranjado16/1623.479612451.494trenzado3LNpor metro40393910037487
18699000BZ
(N)HXCH FE180 E30-E60 4 x 25/16B2ca-s1a,d1,a1anaranjado25/1627.2114217422.106trenzado3LNpor metro40393910037470
18699100BZ
(N)HXCH FE180 E30-E60 4 x 35/16B2ca-s1a,d1,a1anaranjado35/1629.8152621972.432trenzado3LNpor metro40393910037463
18699200BZ
(N)HXCH FE180 E30-E60 4 x 50/25B2ca-s1a,d1,a1anaranjado50/2534.8220330263.298trenzado3LNpor metro40393910037456
18699300BZ
(N)HXCH FE180 E30-E60 4 x 70/35B2ca-s1a,d1,a1anaranjado70/3539.5308241283.968trenzado3LNpor metro40393910037449
18699400BZ
(N)HXCH FE180 E30-E60 4 x 95/50B2ca-s1a,d1,a1anaranjado95/5045.2420855035.298trenzado3LNpor metro40393910037432
18699500BZ
(N)HXCH FE180 E30-E60 4 x 120/70B2ca-s1a,d1,a1anaranjado120/7049.1538868636.051trenzado3LNpor metro40393910037425
18699600BZ
(N)HXCH FE180 E30-E60 4 x 150/70B2ca-s1a,d1,a1anaranjado150/7054.3654083996.971trenzado3LNpor metro40393910037418
18699700BZ
(N)HXCH FE180 E30-E60 4 x 185/95B2ca-s1a,d1,a1anaranjado185/9559.88159104709.075trenzado3LNpor metro40393910037401
18699800BZ
(N)HXCH FE180 E30-E60 4 x 240/120B2ca-s1a,d1,a1anaranjado240/12067.9105461360011.41trenzado3LNpor metro40393910037395
18724402BZ
(N)HXCH FE180 E30-E60 7 x 1.5/2.5B2ca-s1b,d1,a1anaranjado1.5/2.516.11333900.884de corrido7Lpor metro40393910037227

Especificaciones técnicas

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E60* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V. Permitted operating temperature at conductor of +90˚C. Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
Radio de flexión mínimo permanente (multinúcleo) 12 x D
Plegado mínimo durante la instalación (núcleo único) 15 x D
Radio de flexión mínimo permanente (núcleo único) 15 x D
Mínimo de flexión durante la instalación (multinúcleo) 12 x D
Screened no
Integridad del aislamiento FE 180
Integridad de circuito E30-E60*
Temperatura de instalación -5 °C - +50 °C
Temperatura de funcionamiento -45 °C - +90 °C
Tensión de prueba a 50 Hz 4000
Tensión nominal 0.6/1kV
Impresión de aplicaciones For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
System Circuit Integrity is dependent on installation method.
Conductor Cobre desnudo, sólido o trenzado, IEC 60228 y EN 60228 (VDE 0295)
Aislamiento Aislamiento doble, reticulado, compuesto especial de Keram de alto rendimiento, VDE 0266 "HXI1"
Colores principales CENELEC HD 308 S2, VDE 0293
Separator Plastic tape
Relleno Compuesto termoplástico retardante de la llama, libre de halógenos
Conductor concéntrico Bare copper wires with reinforced helix
Material exterior de la vaina Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Color de la funda exterior anaranjado
Integridad de circuito IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutos), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
Integridad del Sistema de Circuito DIN 4102-12, AREI-RGIE Art.104-FR2
Reacción al fuego EN 13501-6
Euroclase B2ca
Densidad de humo EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Cero halógeno gases no corrosivos EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Propagación de llamas EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
Dispersión de llamas EN 60332-3-22/-24, IEC 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2