FE180 E30
Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
in accordance to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
30 minutes system circuit integrity* with reference to DIN 4102-12
1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Sheath: FRNC/LSZH






Variantes de productos y existencias
Descargar
Artículo No. | Stock | Prodotto | Número de núcleos | Diámetro [mm2] | Diámetro exterior de la vaina [mm] | Prop. CU [kg/km] | Peso [kg/km] | Carga de fuego [kWh/m] | Conductor | Construcción | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|
191118 | FE180 E30 2 x 1.5 | 2 | 1.5 | 7.8 | 29 | 102 | 0.22 | de corrido | LN | 40393910069662 | |
188360 | FE180 E30 2 x 1,5 | 2 | 1.5 | 7.8 | 29 | 102 | 0.22 | de corrido | 2L | 40393910072242 | |
191119 | FE180 E30 2 x 2.5 | 2 | 2.5 | 9 | 48 | 142 | 0.28 | de corrido | LN | 40393910069655 | |
190402 | FE180 E30 2 x 2,5 | 2 | 2.5 | 9 | 48 | 142 | 0.28 | de corrido | 2L | 40393910070996 | |
187180 | FE180 E30 3 x 1.5 | 3 | 1.5 | 8.3 | 43 | 121 | 0.25 | de corrido | LNPE | 40393910074499 | |
187184 | FE180 E30 3 x 2.5 | 3 | 2.5 | 9.5 | 72 | 169 | 0.31 | de corrido | LNPE | 40393910074451 | |
187187 | FE180 E30 3 x 4 | 3 | 4 | 11 | 115 | 243 | 0.41 | de corrido | LNPE | 40393910074420 | |
187189 | FE180 E30 3 x 6 | 3 | 6 | 12.5 | 173 | 329 | 0.51 | de corrido | LNPE | 40393910074406 | |
187182 | FE180 E30 4 x 1.5 | 4 | 1.5 | 9.1 | 58 | 147 | 0.29 | de corrido | 3LPE | 40393910074475 | |
190502 | FE180 E30 4 x 2.5 | 4 | 2.5 | 10.5 | 96 | 209 | 0.38 | de corrido | 3LPE | 40393910070828 | |
192352 | FE180 E30 4 x 4 | 4 | 4 | 12.2 | 154 | 304 | 0.49 | de corrido | 3LPE | 40393910067705 | |
192353 | FE180 E30 4 x 6 | 4 | 6 | 13.8 | 230 | 409 | 0.61 | de corrido | 3LPE | 40393910067699 | |
187183 | FE180 E30 5 x 1.5 | 5 | 1.5 | 9.9 | 72 | 177 | 0.35 | de corrido | 3LNPE | 40393910074468 | |
187186 | FE180 E30 5 x 2.5 | 5 | 2.5 | 11.6 | 120 | 255 | 0.47 | de corrido | 3LNPE | 40393910074437 | |
187188 | FE180 E30 5 x 4 | 5 | 4 | 13.4 | 192 | 371 | 0.61 | de corrido | 3LNPE | 40393910074413 | |
187190 | FE180 E30 5 x 6 | 5 | 6 | 15.2 | 288 | 504 | 0.76 | de corrido | 3LNPE | 40393910074390 | |
186267 | FE180 E30 7 x 1.5 | 7 | 1.5 | 10.8 | 100.8 | 220 | 0.41 | de corrido | 6LPE | 40393910076172 | |
186268 | FE180 E30 7 x 2.5 | 7 | 2.5 | 12.5 | 168 | 319 | 0.53 | de corrido | 6LPE | 40393910076165 | |
187201 | FE180 E30 7 x 6 | 7 | 6 | 16.7 | 403 | 644 | 0.89 | de corrido | 6LPE | 40393910074338 | |
187108 | FE180 E30 8 x 1.5 | 8 | 1.5 | 11.9 | 115 | 258 | 0.48 | de corrido | 7LPE | 40393910074680 | |
188345 | FE180 E30 10 x 1.5 | 10 | 1.5 | 13.8 | 144 | 319 | 0.69 | de corrido | 9LPE | 40393910072372 | |
186269 | FE180 E30 12 x 1.5 | 12 | 1.5 | 14.2 | 172.8 | 364 | 0.66 | de corrido | 11LPE | 40393910076158 | |
192479 | FE180 E30 12 x 2.5 | 12 | 2.5 | 16.7 | 288 | 536 | 0.88 | de corrido | 11LPE | 40393910067354 | |
187109 | FE180 E30 21 x 1.5 | 21 | 1.5 | 17.7 | 303 | 578 | 0.99 | de corrido | 20LPE | 40393910074673 | |
190412 | FE180 E30 27 x 1.5 | 27 | 1.5 | 20.4 | 389 | 752 | 1.30 | de corrido | 26LPE | 40393910070972 |
Especificaciones técnicas
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Radio de flexión mínimo permanente (multinúcleo) | 12 x D |
---|---|
Plegado mínimo durante la instalación (núcleo único) | 15 x D |
Radio de flexión mínimo permanente (núcleo único) | 15 x D |
Mínimo de flexión durante la instalación (multinúcleo) | 12 x D |
Observaciones radio de flexión | 50% reduction if installation at 30°C and with a template |
Integridad del aislamiento | FE 180 |
---|---|
Integridad de circuito | E30 |
Temperatura de instalación | -5 °C - +50 °C |
Temperatura de funcionamiento | -45 °C - +90 °C |
Tensión de prueba a 50 Hz | 3500 |
---|---|
Tensión nominal | 0.6/1kV |
System Circuit Integrity is depemndent on installation method. |
Conductor | Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295) |
---|---|
Aislamiento | Special compound, HD 604 S1 part 5 H |
Colores principales | CENELEC HD 308 S2 |
Relleno | HD 604 S1 part 5 H |
Material exterior de la vaina | Compound, HD 604 S1 part 5 H |
Integridad de circuito | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutos), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1 |
---|---|
Densidad de humo | EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD, SEV TP 20B/3C 3.4.3 |
Cero halógeno gases no corrosivos | EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA, SEV TPV11 |
Propagación de llamas | EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Section 4.3.3 F1, SEV TP 20B/3C 3.4.1.1 |
Dispersión de llamas | EN 60332-3-24, IEC 60332-3-24, VDE 0482-332-3-24, AREI-RGIE Section 4.3.3 F2, SEV TP 20B/3C 3.4.1.3 |