Regresar a la: Cables de seguridad

(N)HXCH FE180 E90 B2ca

halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E90 in accordance with DIN 4102-12
Reacción al fuego según EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

Descripción

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V.
Permitted operating temperature at conductor of +90˚C.

  • For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
  • Color de la funda exterior anaranjado
  • Material exterior de la vaina Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
  • Conductor concéntrico Bare copper wires with reinforced helix
  • Conductor Cobre desnudo, sólido o trenzado, IEC 60228 y EN 60228 (VDE 0295)
  • Colores principales CENELEC HD 308 S2, VDE 0293
  • Relleno Compuesto libre de halógenos o cinta plástica
  • Aislamiento Aislamiento doble, reticulado, compuesto especial de Keram de alto rendimiento, VDE 0266 "HXI1"
  • Reacción al fuego (Euroclases) EN 13501-6: B2ca
  • Cero halógeno gases no corrosivos IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
  • Propagación de llamas IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2, AREI-RGIE Art.104-F1
  • Dispersión de llamas IEC 60332-3-22/-24 Cat. A/C, EN 60332-3-22/-24 Cat. A/C, VDE 0482-332-3-22/-24 Cat. A/C, AREI-RGIE Art.104-F2
  • Densidad de humo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
  • Integridad del Sistema de Circuito DIN 4102-12, VdS 3423 (Single-core more than 16.0 mm²), AREI-RGIE Art.104-FR2
  • Integridad de circuito (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), VDE 0482-362, AREI-RGIE Art.104-FR1
  • System Circuit Integrity is dependent on installation method.
  • Tensión de prueba a 50 Hz 4000 V
  • Temperatura de instalación -5 °C - +50 °C
  • Temperatura de funcionamiento -45 °C - +90 °C
  • Integridad de circuito E90
  • Integridad del aislamiento FE 180
  • Mínimo de flexión durante la instalación (multinúcleo) 12 x D
  • Radio de flexión mínimo permanente (multinúcleo) 12 x D

Documentos

ENDENLFRCNESIT
Certificado MPA file-icon Certificado MPA file-icon file-icon file-icon file-icon file-icon
CoC CoC CoC file-icon file-icon file-icon file-icon file-icon file-icon
DAT_VDEApproval_OBJ DAT_VDEApproval_OBJ file-icon file-icon file-icon file-icon file-icon file-icon
Ficha técnica Ficha técnica Ficha técnica Ficha técnica Ficha técnica file-icon Ficha técnica Ficha técnica

Versiones

N° de artículoInventarioProductoReacción al fuegoColor de la funda exteriorNúmero de núcleosDiámetro [mm2]Diámetro exterior de la vaina [mm]Prop. CU [kg/km]Peso [kg/km]Carga de fuego [kWh/m]ConductorConstrucciónUnidad de embalaje
18607100BZ (N)HXCH FE180 E90 3 x 1.5/1.5B2ca-s1a,d1,a1anaranjado31.5/1.513.2 mm662470.599 kWh/mde corrido3Lpor metro
18619500BZ (N)HXCH FE180 E90 3 x 2.5/2.5B2ca-s1a,d1,a1anaranjado32.5/2.514.1 mm1043050.784 kWh/mde corrido3Lpor metro
18619700BZ (N)HXCH FE180 E90 3 x 4/4B2ca-s1a,d1,a1anaranjado34/415.6 mm1614010.771 kWh/mde corrido3Lpor metro
18727800BZ (N)HXCH FE180 E90 3 x 6/6B2ca-s1a,d1,a1anaranjado36/616.9 mm2405230.921 kWh/mde corrido3Lpor metro
17241700BZ (N)HXCH FE180 E90 3 x 35/16B2ca-s1a,d1,a1anaranjado335/1629 mm119019442.267 kWh/mtrenzado3Lpor metro
18740800BZ (N)HXCH FE180 E90 3 x 50/25B2ca-s1a,d1,a1anaranjado350/2532.5 mm172325492.729 kWh/mtrenzado3Lpor metro
18740900BZ (N)HXCH FE180 E90 3 x 70/35B2ca-s1a,d1,a1anaranjado370/3537.6 mm241035403.542 kWh/mtrenzado3Lpor metro
18741000BZ (N)HXCH FE180 E90 3 x 95/50B2ca-s1a,d1,a1anaranjado395/5041.9 mm329646044.285 kWh/mtrenzado3Lpor metro
18741100BZ (N)HXCH FE180 E90 3 x 120/70B2ca-s1a,d1,a1anaranjado3120/7045.3 mm423656945.112 kWh/mtrenzado3Lpor metro
18741200BZ (N)HXCH FE180 E90 3 x 150/70B2ca-s1a,d1,a1anaranjado3150/7050 mm510069195.889 kWh/mtrenzado3Lpor metro
18607200BZ (N)HXCH FE180 E90 4 x 1.5/1.5B2ca-s1a,d1,a1anaranjado41.5/1.514.1 mm812820.677 kWh/mde corrido3LNpor metro
18619600BZ (N)HXCH FE180 E90 4 x 2.5/2.5B2ca-s1a,d1,a1anaranjado42.5/2.515.1 mm1283510.754 kWh/mde corrido3LNpor metro
18619800BZ (N)HXCH FE180 E90 4 x 4/4B2ca-s1a,d1,a1anaranjado44/416.7 mm2004660.87 kWh/mde corrido3LNpor metro
18619900BZ (N)HXCH FE180 E90 4 x 6/6B2ca-s1a,d1,a1anaranjado46/618.1 mm2976141.051 kWh/mde corrido3LNpor metro
18620000BZ (N)HXCH FE180 E90 4 x 10/10B2ca-s1a,d1,a1anaranjado410/1020.1 mm5048671.25 kWh/mde corrido3LNpor metro
18613100BZ (N)HXCH FE180 E90 4 x 16/16B2ca-s1a,d1,a1anaranjado416/1625.3 mm79613991.772 kWh/mtrenzado3LNpor metro
18613200BZ (N)HXCH FE180 E90 4 x 25/16B2ca-s1a,d1,a1anaranjado425/1628.9 mm114218992.568 kWh/mtrenzado3LNpor metro
18613300BZ (N)HXCH FE180 E90 4 x 35/16B2ca-s1a,d1,a1anaranjado435/1631.6 mm152623822.568 kWh/mtrenzado3LNpor metro
18613400BZ (N)HXCH FE180 E90 4 x 50/25B2ca-s1a,d1,a1anaranjado450/2536.7 mm220332493.374 kWh/mtrenzado3LNpor metro
18613500BZ (N)HXCH FE180 E90 4 x 70/35B2ca-s1a,d1,a1anaranjado470/3541.3 mm308243764.08 kWh/mtrenzado3LNpor metro
18613600BZ (N)HXCH FE180 E90 4 x 95/50B2ca-s1a,d1,a1anaranjado495/5046.4 mm420857375.179 kWh/mtrenzado3LNpor metro
18613700BZ (N)HXCH FE180 E90 4 x 120/70B2ca-s1a,d1,a1anaranjado4120/7050.1 mm538870855.858 kWh/mtrenzado3LNpor metro
18613800BZ (N)HXCH FE180 E90 4 x 150/70B2ca-s1a,d1,a1anaranjado4150/7055.3 mm654086407.11 kWh/mtrenzado3LNpor metro
18613900BZ (N)HXCH FE180 E90 4 x 185/95B2ca-s1a,d1,a1anaranjado4185/9560.8 mm8159107378.61 kWh/mtrenzado3LNpor metro
18614000BZ (N)HXCH FE180 E90 4 x 240/120B2ca-s1a,d1,a1anaranjado4240/12069.2 mm105461396110.885 kWh/mtrenzado3LNpor metro
18607302BZ (N)HXCH FE180 E90 7 x 1.5/2.5B2ca-s1b,d1,a1anaranjado71.5/2.516.1 mm1333910.884 kWh/mde corrido7Lpor metro
19109602BZ (N)HXCH FE180 E90 7 x 2.5/2.5B2ca-s1b,d1,a1anaranjado72.5/2.517.3 mm2004860.994 kWh/mde corrido7Lpor metro
18741502BZ (N)HXCH FE180 E90 12 x 1.5/2.5B2ca-s1b,d1,a1anaranjado121.5/2.520.2 mm205.85911.308 kWh/mde corrido12Lpor metro