CU 7702 4P FRNC/GG/FRNC

Data cable, S/FTP, Category 7A, AWG22, Euroclass Cca
1300 MHz

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.52 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Sheath: FRNC/LS0H orange RAL 2003
6 Rodent protection: with glass rovings
7 Ripcord
8 Outer sheath: FRNC/LS0H black

01_RoHS 04_Propagation 02_PoEp_gn 10_Schielded_EN 06_Density 03_LS0H CPR_Cca CPR_Dca CPR_Eca CPR_Fca

Varianti di prodotto e stock

Articolo n. Stock ProdottoReaction to fireDimensions n x p x [mm (AWG)]Dimensioni della guaina esterna [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]Unità di imballaggioGTIN / EAN
19435400CZ
CU 7702 4PCca-s1a,d1,a14 x 2 x 0.62 (AWG22)12.034.9166.60.55al metro40393910022704

Specifiche tecniche

Applicable for outdoor installation due to rodent protection and UV resistant outer cable sheath.
Robust cable design with a high mechanical stability.
Electrically and mechanically superior quality Cat.7A data cable - exceeds the requirements of ISO/IEC 11801-1, IEC 61156-5, EN 50173-1 and EN 50288-9-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801-1.
Curvatura minima (durante l'installazione) 96 mm
Resistenza alla trazione (4P) 150 N
Minimum number of impacts 10
Resistenza minima allo schiacciamento / 10cm 1000 N
AWG 22
Solid / Flex stabile
Raggio di curvatura minimo (installato in modo permanente) 48 mm
Data cable for structured premise cabling with enhanced mechanical and fire protection performance.
Designed for installation in Tunnels, Metro-Systems and Buildings with augmented requirements.
With rodent protection and UV protected outer sheath. Installation in ducts, tubes and on cable support systems.
Suitable for all ICT network applications up to class FA applications (1000 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Supports 10Base-T, 100Base-T, 1GBase-T (1000Base-T) and 10GBase-T.
Applicable for Power over Ethernet PoE / PoE+ / 4PPoE.
Categoria Cat.7A
GBit/s A 10 Gbit/s
Loop resistance at 20 °C 116 Ω/km
Operating capacity 43 pF/m
Impedenza a 100 MHz, ±5Ω 100 Ω
NVP % 76
Ritardo Skew 15 ns/100 m
Schermatura schermati
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
Transfer impedance 1/10/30 MHz < 5/5/8 mΩ/m
Attenuazione di accoppiamento 85 dB
Segregation class d
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Colore del filo bianco/blu-bianco, bianco/arancio-bianco, bianco/verde-bianco, bianco/marrone-bianco (con strisce longitudinali)
Impronta DATWYLER «cable type» «additional text» «batch number» «meter marks»
Campo di applicazione All'aperto
Reaction to fire EN 13501-6
Euroclass Cca
Densità del fumo IEC 61034-1/-2, EN 61034-1/-2
Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2
Propagazione della fiamma EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Standard dei cavi ISO/IEC 61156-5, EN 50288-9-1
Cat./Class Cat.7A / Class FA
PoE IEEE 802.3bt Type 4 (100W)
Materiale della guaina esterna FRNC/LSZH
Colore della guaina esterna nero

Documentazione