CU 6052 4P / 2x4P F8
Data cable, F/FTP, Category 6, AWG23, Euroclass Dca
300 MHz
1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.3 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Alu PETP foil
5 Drain wire: Tinned copper wire
6 Outer sheath: FRNC/LSOH Orange RAL 2003











Varianti di prodotto e stock
Scaricare
Articolo n. | Stock | Prodotto | Reaction to fire | Dimensions n x p x [mm (AWG)] | Dimensioni della guaina esterna [mm] | Tasso di CU [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Unità di imballaggio | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|
18851200DK | CU 6052 4P | Dca-s2,d1,a1 | 4 x 2 x 0.55 (AWG23) | 7 | 20.0 | 48.4 | 0.144 | 1000 m tamburo | 40393910034356 | |
18851300DL | CU 6052 2x4P | Dca-s2,d1,a1 | 2 x (4 x 2 x 0.55 (AWG23)) | 7.0 x 14.8 | 40.0 | 97.6 | 0.225 | 500 m tamburo | 40393910034325 |
Specifiche tecniche
Electrically and mechanically superior quality Cat.6 data cable - exceeds the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-5-1.
Good shielding effect due to individually screened pairs and overall foil screen.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Good shielding effect due to individually screened pairs and overall foil screen.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Curvatura minima (durante l'installazione) | 56 mm |
---|---|
Resistenza alla trazione (2x4P) | 190 N |
Resistenza alla trazione (4P) | 95 N |
Minimum number of impacts | 10 |
Resistenza minima allo schiacciamento / 10cm | 1000 N |
AWG | 23 |
Solid / Flex | stabile |
Raggio di curvatura minimo (installato in modo permanente) | 28 mm |
Data cable for structured premises cabling. For the transmission of digital and analogue voice, video and data signals. Suitable for all ICT network applications up to class E applications (250 MHz) in accordance with EN 50173-1 and ISO/IEC 11801. Applicable for Power over Ethernet (PoE) / PoE+. |
Categoria | Cat.6 |
---|---|
GBit/s | A 1 Gbit/s |
Loop resistance at 20 °C | 150 Ω/km |
Operating capacity | 42 pF/m |
Impedenza a 100 MHz, ±5Ω | 100 Ω |
NVP % | 79 |
Ritardo Skew | 5 ns/100 m |
Schermatura | schermati |
Near end unbalance attenuation LCL at 1-600 MHz | 40 dB |
Transfer impedance 1/10/30 MHz | < 50/100/200 mΩ/m |
Attenuazione di accoppiamento | 65 dB |
Segregation class | c |
Temperatura di installazione | 0 °C - +50 °C |
---|---|
Temperatura di esercizio | -20 °C - +60 °C |
Colore del filo | bianco/blu, bianco/arancio, bianco/verde, bianco/marrone, in conformità alle norme IEC 60189 e IEC 60708 |
Marcatura | DATWYLER «cable type» «additional text» «batch number» «meter marks» |
Campo di applicazione | Interno |
Reazione al fuoco | EN 13501-6 |
---|---|
Classe Euro | Dca |
Densità dei fumi | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD |
Senza alogeni, gas non corrosivi | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA |
Propagazione della fiamma | AREI-RGIE Section 4.3.3 F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2 |
Diffusione della fiamma | IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Section 4.3.3 F2 |
Standard dei cavi | ISO/IEC 61156-5, EN 50288-5-1 |
Cat./Classe | Cat.6 / Class E |
PoE (Power over Ethernet) | IEEE 802.3bt Type 4 (100W) |
Materiale della guaina esterna | FRNC/LSZH |
---|---|
Colore della guaina esterna | arancia |