Safety cable, 0.6/1kV, Keram
Halogen-free, with improved fire characteristics;
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
System Circuit Integrity is provided up to 400 V operating voltage.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core)
12 x D
Curvatura minima durante l'installazione (anima singola)
15 x D
Minimum bending radius permanent (single core)
15 x D
Curvatura minima durante l'installazione (multicore)
12 x D
Remarks bending radius
50% reduction if installation at 30°C and with a template
Integrità dell'isolamento
FE 180
Integrità del circuito
E30-E60*
Installation temperature
-5 °C - +50 °C
Operating temperature
-45 °C - +90 °C
Tensione di prova a 50Hz
3500
Nominal voltage
0.6/1kV
* System Circuit Integrity is dependent on installation method
Conduttore
Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Isolamento
Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Colori delle anime
CENELEC HD 308 S2(≥16 mm2: CENELEC HD 308 S2, VDE 0293)
Riempitrice
HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Materiale della guaina esterna
Compound, HD 604 S1 part 5 H(16 mm2: polyolefin compound in accordance with VDE 0276-604, CENELEC HD 604 S1 "HM4", flame-retardant)