(N)HXH CL FE180 E30-E60

Safety cable, 0.6/1kV armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Inner sheath: Polyolefin, flame retardant, low smoke, zero halogen
6 Armouring: galvanised steel tape
7 Sheath: FRNC/LSZH

07_Circuit 03_LS0H 08_System 05_Spread 04_Propagation 06_Density

Varianti di prodotto e stock

Articolo n. Stock ProdottoColore della guaina esternaDiametro mm²Diametro esterno della guaina [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionGTIN / EAN
196453
(N)HXH-J CL FE180 E30-E60 3 x 4nero181155071.22solidLNPE40393910060775
192724
(N)HXH-J CL FE180 E30-E60 5 x 2.5nero2.5191205451.38solid3LNPE40393910066647

Specifiche tecniche

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of Circuit Integrity E30-E60* in accordance with DIN 4102-12. Circuit Integrity is guaranteed at an operating voltage up to 400V. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 12 x D
Curvatura minima durante l'installazione (anima singola) 15 x D
Minimum bending radius permanent (single core) 15 x D
Curvatura minima durante l'installazione (multicore) 12 x D
Integrità dell'isolamento FE 180
Integrità del circuito E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Tensione di prova a 50Hz 4000
Nominal voltage 0.6/1kV
System Circuit Integrity is dependent on installation method.
Conduttore Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Isolamento Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Colori delle anime CENELEC HD 308 S2, VDE 0293
Riempitrice Flame retardant, halogen-free thermoplastic compound
Guaina interna Flame retardant Polyolefin compound,CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Armatura (protezione per roditori) Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Materiale della guaina esterna Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Integrità del circuito IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
Integrità del circuito di sistema DIN 4102-12, AREI-RGIE Art.104-FR2
Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Propagazione della fiamma AREI-RGIE Art.104-F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentazione