(N)HXCH FE180 E30-E60 B2ca

Safety cable, 0.6/1kV, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0266 and CENELEC HD 604 S1,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331,
System Circuit Integrity E30-E60* in accordance with DIN 4102-12
Reaction to fire according to EN 13501-6

1 Conductor: solid/stranded
2 Fire barrier: high-peformance Keram compound
3 Insulation: cross-linked polymer, zero halogen
4 Filler: flame retardant, zero halogen
5 Concentric conductor: bare copper wire
6 Reinforcing helix: bare copper tape
7 Separator: plastic tape
8 Sheath: FRNC/LSZH

07_Circuit 08_System 05_Spread 06_Density 03_LS0H 04_Propagation

Varianti di prodotto e stock

Articolo n. Stock ProdottoReaction to fireColore della guaina esternaDiametro mm²Diametro esterno della guaina [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]ConductorConstructionUnità di imballaggioGTIN / EAN
18694300BZ
(N)HXCH FE180 E30-E60 2 x 1.5/1.5B2ca-s1a,d1,a1arancia1.5/1.512.7522210.551solidLNal metro40393910037883
18694400BZ
(N)HXCH FE180 E30-E60 2 x 2.5/2.5B2ca-s1a,d1,a1arancia2.5/2.513.5802690.612solidLNal metro40393910037876
18723200BZ
(N)HXCH FE180 E30-E60 2 x 4/4B2ca-s1a,d1,a1arancia4/414.91233500.706solidLNal metro40393910037296
18723400BZ
(N)HXCH FE180 E30-E60 2 x 6/6B2ca-s1a,d1,a1arancia6/6161824280.79solidLNal metro40393910037289
18694500BZ
(N)HXCH FE180 E30-E60 3 x 1.5/1.5B2ca-s1a,d1,a1arancia1.5/1.513.2662460.599solid3Lal metro40393910037869
18694600BZ
(N)HXCH FE180 E30-E60 3 x 2.5/2.5B2ca-s1a,d1,a1arancia2.5/2.514.11043030.784solid3Lal metro40393910037852
18723800BZ
(N)HXCH FE180 E30-E60 3 x 16/16B2ca-s1a,d1,a1arancia16/1621.3624.710271.348stranded3Lal metro40393910037272
18723900BZ
(N)HXCH FE180 E30-E60 3 x 25/16B2ca-s1a,d1,a1arancia25/162590214331.799stranded3Lal metro40393910037265
18724000BZ
(N)HXCH FE180 E30-E60 3 x 35/16B2ca-s1a,d1,a1arancia35/1637.3119017992.096stranded3Lal metro40393910037258
18724100BZ
(N)HXCH FE180 E30-E60 3 x 50/25B2ca-s1a,d1,a1arancia50/2531.7172324502.689stranded3Lal metro40393910037241
18724200BZ
(N)HXCH FE180 E30-E60 3 x 70/35B2ca-s1a,d1,a1arancia70/3536241033423.32stranded3Lal metro40393910037234
18698500BZ
(N)HXCH FE180 E30-E60 3 x 95/50B2ca-s1a,d1,a1arancia95/5041.1329644454.416stranded3Lal metro40393910037524
18698600BZ
(N)HXCH FE180 E30-E60 3 x 120/70B2ca-s1a,d1,a1arancia120/7044.5423655245.002stranded3Lal metro40393910037517
18698700BZ
(N)HXCH FE180 E30-E60 3 x 150/70B2ca-s1a,d1,a1arancia150/7049.2510067306.114stranded3Lal metro40393910037500
18698800BZ
(N)HXCH FE180 E30-E60 3 x 240/120B2ca-s1a,d1,a1arancia240/12061.58242109089.391stranded3Lal metro40393910037494
18694700BZ
(N)HXCH FE180 E30-E60 4 x 1.5/1.5B2ca-s1a,d1,a1arancia1.5/1.514.1812800.677solid3LNal metro40393910037845
18694800BZ
(N)HXCH FE180 E30-E60 4 x 2.5/2.5B2ca-s1a,d1,a1arancia2.5/2.515.11283500.754solid3LNal metro40393910037838
18694900BZ
(N)HXCH FE180 E30-E60 4 x 4/4B2ca-s1a,d1,a1arancia4/416.72004640.87solid3LNal metro40393910037821
18695000BZ
(N)HXCH FE180 E30-E60 4 x 6/6B2ca-s1a,d1,a1arancia6/618.12976121.051solid3LNal metro40393910037814
18695100BZ
(N)HXCH FE180 E30-E60 4 x 10/10B2ca-s1a,d1,a1arancia10/1020.15048581.25solid3LNal metro40393910037807
18698900BZ
(N)HXCH FE180 E30-E60 4 x 16/16B2ca-s1a,d1,a1arancia16/1623.479612451.494stranded3LNal metro40393910037487
18699000BZ
(N)HXCH FE180 E30-E60 4 x 25/16B2ca-s1a,d1,a1arancia25/1627.2114217422.106stranded3LNal metro40393910037470
18699100BZ
(N)HXCH FE180 E30-E60 4 x 35/16B2ca-s1a,d1,a1arancia35/1629.8152621972.432stranded3LNal metro40393910037463
18699200BZ
(N)HXCH FE180 E30-E60 4 x 50/25B2ca-s1a,d1,a1arancia50/2534.8220330263.298stranded3LNal metro40393910037456
18699300BZ
(N)HXCH FE180 E30-E60 4 x 70/35B2ca-s1a,d1,a1arancia70/3539.5308241283.968stranded3LNal metro40393910037449
18699400BZ
(N)HXCH FE180 E30-E60 4 x 95/50B2ca-s1a,d1,a1arancia95/5045.2420855035.298stranded3LNal metro40393910037432
18699500BZ
(N)HXCH FE180 E30-E60 4 x 120/70B2ca-s1a,d1,a1arancia120/7049.1538868636.051stranded3LNal metro40393910037425
18699600BZ
(N)HXCH FE180 E30-E60 4 x 150/70B2ca-s1a,d1,a1arancia150/7054.3654083996.971stranded3LNal metro40393910037418
18699700BZ
(N)HXCH FE180 E30-E60 4 x 185/95B2ca-s1a,d1,a1arancia185/9559.88159104709.075stranded3LNal metro40393910037401
18699800BZ
(N)HXCH FE180 E30-E60 4 x 240/120B2ca-s1a,d1,a1arancia240/12067.9105461360011.41stranded3LNal metro40393910037395
18724402BZ
(N)HXCH FE180 E30-E60 7 x 1.5/2.5B2ca-s1b,d1,a1arancia1.5/2.516.11333900.884solid7Lal metro40393910037227

Specifiche tecniche

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E60* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 400V. Permitted operating temperature at conductor of +90˚C. Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
Minimum bending radius permanent (multi core) 12 x D
Curvatura minima durante l'installazione (anima singola) 15 x D
Minimum bending radius permanent (single core) 15 x D
Curvatura minima durante l'installazione (multicore) 12 x D
Screened no
Integrità dell'isolamento FE 180
Integrità del circuito E30-E60*
Installation temperature -5 °C - +50 °C
Operating temperature -45 °C - +90 °C
Tensione di prova a 50Hz 4000
Nominal voltage 0.6/1kV
For use in critical fire safety infrastructure (in compliance with VKF, ASTRA, Tunnels Directive, etc.), particularly in escape routes and emergency lines.
System Circuit Integrity is dependent on installation method.
Conduttore Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295)
Isolamento Double insulation, cross-linked, high-performance Keram special compound, VDE 0266 "HXI1"
Colori delle anime CENELEC HD 308 S2, VDE 0293
Separator Plastic tape
Riempitrice Flame retardant, halogen-free thermoplastic compound
Conduttore concentrico Bare copper wires with reinforced helix
Materiale della guaina esterna Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4"
Colore della guaina esterna arancia
Integrità del circuito IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), VDE 0482-200 (PH120), AREI-RGIE Art.104-FR1
Integrità del circuito di sistema DIN 4102-12, AREI-RGIE Art.104-FR2
Reaction to fire EN 13501-6
Euroclass B2ca
Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD
Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA
Propagazione della fiamma AREI-RGIE Art.104-F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Art.104-F2

Documentazione