N2XCH
Safety cable, 0.6/1kV, Euroclass Cca
halogen-free, with improved fire characteristics,
CENELEC HD 604 S1, VDE 0276-604
1 Conductor: solid/ stranded
2 Insulation: cross-linked PE, zero halogen
3 Filler: flame retardant, zero halogen
4 Concentric conductor: bare copper wire
5 Reinforcing helix: bare copper tape
6 Separator: plastic tape
7 Sheath: FRNC/LSZH
Varianti di prodotto e stock
Articolo n. | Stock | Prodotto | Reaction to fire | Diametro mm² | Diametro esterno della guaina [mm] | Tasso di CU [kg/km] | Weight [kg/km] | Fire load [kWh/m] | Conductor | Construction | Unità di imballaggio | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|---|---|---|
17017204CZ | N2XCH 3 x 50/25 | Cca-s1,d1,a1 | 50/25 | 29 | 1723 | 1990 | 2.72 | solid | 3L | al metro | 40393910100082 | |
17017404CZ | N2XCH 3 x 120/70 | Cca-s1,d1,a1 | 120/70 | 41.6 | 4236 | 5270 | 5.55 | stranded | 3L | al metro | 40393910100051 | |
17017504CZ | N2XCH 3 x 70/35 | Cca-s1,d1,a1 | 70/35 | 34.8 | 2410 | 2830 | 4.11 | stranded | 3L | al metro | 40393910100037 | |
17018404CZ | N2XCH 4 x 50/25 | Cca-s1,d1,a1 | 50/25 | 34.4 | 2203 | 2600 | 3.38 | stranded | 3LN | al metro | 40393910099966 | |
17018504CZ | N2XCH 4 x 70/35 | Cca-s1,d1,a1 | 70/35 | 40.5 | 3082 | 3550 | 4.48 | stranded | 3LN | al metro | 40393910099942 | |
17018604CZ | N2XCH 4 x 95/50 | Cca-s1,d1,a1 | 95/50 | 44.4 | 4208 | 4800 | 5.44 | stranded | 3LN | al metro | 40393910099911 | |
17018704CZ | N2XCH 4 x 120/70 | Cca-s1,d1,a1 | 120/70 | 48.3 | 5382 | 6500 | 6.38 | stranded | 3LN | al metro | 40393910099898 | |
17018804CZ | N2XCH 4 x 150/70 | Cca-s1,d1,a1 | 150/70 | 53.2 | 6540 | 7950 | 7.97 | stranded | 3LN | al metro | 40393910099874 | |
17018904CZ | N2XCH 4 x 185/95 | Cca-s1,d1,a1 | 185/95 | 58.9 | 8159 | 9970 | 9.86 | stranded | 3LN | al metro | 40393910099843 | |
17019704CZ | N2XCH 3 x 95/50 | Cca-s1,d1,a1 | 95/50 | 37.7 | 3296 | 4350 | 4.60 | stranded | 3L | al metro | 40393910099805 | |
17019804CZ | N2XCH 3 x 150/70 | Cca-s1,d1,a1 | 150/70 | 45.6 | 5100 | 5450 | 6.68 | stranded | 3L | al metro | 40393910099782 |
Specifiche tecniche
For permanent installation in dry, damp or wet areas, on or behind plasterwork or in walls or concrete. Also suitable for outdoor applications.
The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) | 12 x D |
---|---|
Curvatura minima durante l'installazione (multicore) | 12 x D |
Remarks bending radius | *50% reduction if installation at 30°C and with a template |
Integrità dell'isolamento | No |
---|---|
Integrità del circuito | No |
Installation temperature | -5 °C - +50 °C |
Operating temperature | -45 °C - +90 °C |
Impronta | Sur demande |
Conduttore | Bare copper, solid or stranded, IEC 60228 and EN 60228 (VDE 0295) |
---|---|
Isolamento | Cross-linked Polyethylene, CENELEC HD 604 S1 and VDE 0276-604 |
Colori delle anime | CENELEC HD 308 S2, VDE 0293 |
Riempitrice | Halogen-free compound or plastic tape |
Conduttore concentrico | Bare copper wires with reinforced helix |
Materiale della guaina esterna | Flame retardant Polyolefin compound, CENELEC HD 604 S1 and VDE 0276-604 "HM4" |
Reaction to fire | EN 13501-6 |
---|---|
Euroclass | Cca |
Densità del fumo | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Art.104-SD |
Zero alogeni nessun gas corrosivo | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Art.104-SA |
Propagazione della fiamma | AREI-RGIE Art.104-F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2 |
Flame spread | IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Art.104-F2 |
Documentazione
-
Scheda tecnica
Scaricare PDF [ 139,917 KB ]
-
Scheda tecnica
Scaricare PDF [ 141,485 KB ]
-
Scheda tecnica
Scaricare PDF [ 140,513 KB ]
-
Scheda tecnica
Scaricare PDF [ 140,901 KB ]
-
Scheda tecnica
Scaricare PDF [ 140,613 KB ]
-
Scheda tecnica
Scaricare PDF [ 141,7 KB ]
-
Scheda tecnica
Scaricare PDF [ 143,635 KB ]