Fire alarm cable with steel wire braiding, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 2x2x0,8 mm
rosso
2
9.2
25
125.1
0.26
al metro
40393910072921
188120
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 4x2x0,8 mm
rosso
2
12
45
190.3
0.39
al metro
40393910072914
188127
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 8x2x0,8 mm
rosso
2
18.2
85
419.7
0.93
al metro
40393910072877
188128
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 12x2x0,8 mm
rosso
2
19.1
126
491.6
1.01
al metro
40393910072860
188129
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 20x2x0,8 mm
rosso
2
22.5
206
680.6
1.32
al metro
40393910072853
188346
JE-H(St)HRH...Bd FE180 E30-E90 fire alarm 32x2x0,8 mm
rosso
2
26.7
326
920.3
1.72
al metro
40393910072365
Specifiche tecniche
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The steel wire braiding serves as mechanical protection. The fire alarm cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70°C.
operating capacity, 1km @ 800Hz
120
Test voltage 50Hz, core/core
500
peak voltage
225
Capacitive coupling 0,8 mm, 100m @ 800Hz
200
resistenza massima del loop 0,8 mm
73.2
Minimum insulation resistance
100
Test voltage 50Hz, core/screen
2000
Integrità dell'isolamento
FE 180
Integrità del circuito
E90
Installation temperature
-5 °C - +50 °C
Operating temperature
-30 °C - +70 °C
Curvatura minima durante l'installazione (multicore)
7.5 x D
Minimum bending radius permanent (multi core)
7.5 x D
Resistenza minima allo schiacciamento / 10cm
1000
N
System Circuit Integrity dependent on installation method.
Conduttore
Bare copper, solid, 0.8 mm diameter, VDE 0815
Isolamento
Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Colori delle anime
VDE 0815
Shielding
Al-laminated tape with copper drain wire Ø 0.8 mm
Guaina interna
Flame retardant polyolefin compound, VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM2"
Armatura (protezione per roditori)
Galvanised steel wire braid
Materiale della guaina esterna
Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"