JE-H(St)H...Bd FE180 E30 L fire alarm

Fire alarm cable, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30* in accordance with DIN 4102-12

1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH

07_Circuit 04_Propagation 05_Spread 06_Density 08_System 03_LS0H

Varianti di prodotto e stock

Articolo n. Stock ProdottoColore della guaina esternaDiametro esterno della guaina [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]Unità di imballaggioGTIN / EAN
18837400ZK
JE-H(St)H...Bd FE180 E30 L fire alarm 2x2x0,8 mmrosso6.125590.1231000 m tamburo40393910035230
18837400ZL
JE-H(St)H...Bd FE180 E30 L fire alarm 2x2x0,8 mmrosso6.125590.123500 m tamburo40393910035223
18837400ZZ
JE-H(St)H...Bd FE180 E30 L fire alarm 2x2x0,8 mmrosso6.325600.123al metro40393910035209
18837700ZP
JE-H(St)H...Bd FE180 E30 L fire alarm 1x2x0,8 mmrosso5.415400.123250 m PullQuick box40393910210767
18837400ZP
JE-H(St)H...Bd FE180 E30 L fire alarm 2x2x0,8 mmrosso6.125600.123250 m PullQuick box40393910210774
188375
JE-H(St)H...Bd FE180 E30 L fire alarm 4x2x0,8 mmrosso945990.21al metro40393910072167

Specifiche tecniche

Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V. Permitted operating temperature at conductor of +70˚C.
operating capacity, 1km @ 800Hz 120
resistenza massima del loop 0,8 mm 73.2
Test voltage 50Hz, core/screen 2000
Minimum insulation resistance 100
Capacitive coupling 0,8 mm, 100m @ 800Hz 200
Test voltage 50Hz, core/core 500
peak voltage 225
Minimum bending radius permanent (multi core) 7.5 x D
Curvatura minima durante l'installazione (multicore) 7.5 x D
Resistenza minima allo schiacciamento / 10cm 1000 N
Integrità dell'isolamento FE 180
Integrità del circuito E30
Installation temperature -5 °C - +50 °C
Operating temperature -30 °C - +70 °C
System Circuit Integrity is dependent on installation method.
Conduttore Bare copper, solid, 0.8 mm diameter, VDE 0815
Isolamento Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Colori delle anime VDE 0815
Shielding Al-laminated tape with copper drain wire Ø 0.8 mm
Materiale della guaina esterna Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"
Integrità del circuito IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-1 (120 minutes), IEC 60331-2 (120 minutes), EN 50200 (PH120 minutes), NBN 713-020, VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1
Integrità del circuito di sistema DIN 4102-12, AREI-RGIE Section 4.3.3 FR2
Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Propagazione della fiamma AREI-RGIE Section 4.3.3 F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2