Fire alarm cable, max. 225V, Keram
halogen-free, with improved fire characteristics,
with reference to VDE 0815,
circuit integrity (FE180) in accordance with VDE 0472-814, IEC 60331, EN 50200,
System Circuit Integrity E30-E90* in accordance with DIN 4102-12
Fire behaviour according to EN 50575, EN 13601-6
1 Conductor: solid
2 Insulation: cross-linked polymer, zero halogen
3 Drain wire: Ø 0.8 mm
4 Separator: plastic tape, zero halogen
5 Shielding: Al-laminated tape, zero halogen
6 Sheath: FRNC/LSZH
Varianti di prodotto e stock
Scaricare
Articolo n.
Stock
Prodotto
Reaction to fire
Numero di core
Diametro esterno della guaina [mm]
Tasso di CU [kg/km]
Weight [kg/km]
Fire load [kWh/m]
Unità di imballaggio
GTIN / EAN
18809300BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 1x2x0,8 mm
B2ca-s1a,d1,a1
2
5.6
15
40.3
0.108
al metro
40393910230277
18809800BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 2x2x0,8 mm
B2ca-s1a,d1,a1
2
6.3
25
58.8
0.138
al metro
40393910230291
18810100BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 4x2x0,8 mm
B2ca-s1a,d1,a1
2
9.0
45
100.5
0.224
al metro
40393910230314
18810300BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 8x2x0,8 mm
B2ca-s1a,d1,a1
2
13.9
85
223.9
0.522
al metro
40393910230338
18810500BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 12x2x0,8 mm
B2ca-s1a,d1,a1
2
14.8
126
285.3
0.605
al metro
40393910230352
18810700BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 16x2x0,8 mm
B2ca-s1a,d1,a1
2
16.6
166
331.1
0.628
al metro
40393910230376
18810900BZ
JE-H(St)H...Bd FE180 E30-E90 fire alarm 20x2x0,8 mm
B2ca-s1a,d1,a1
2
18.8
206
428.4
0.842
al metro
40393910230390
Specifiche tecniche
Cables with intrinsic fire resistance are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled. Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used. These cables correspond to the demands of System Circuit Integrity E30-E90* in accordance with DIN 4102-12. System Circuit Integrity is guaranteed at an operating voltage up to 110V.
Permitted operating temperature at conductor of +70˚C.
Suitable according to VKF fire protection guideline in escape routes and in tunnels according to Astra guideline 13022.
operating capacity, 1km @ 800Hz
120
Test voltage 50Hz, core/core
500
peak voltage
225
Capacitive coupling 0,8 mm, 100m @ 800Hz
200
resistenza massima del loop 0,8 mm
73.2
Minimum insulation resistance
100
Test voltage 50Hz, core/screen
2000
Integrità dell'isolamento
FE 180
Integrità del circuito
E90
Installation temperature
-5 °C - +50 °C
Operating temperature
-30 °C - +70 °C
Curvatura minima durante l'installazione (multicore)
7.5 x D
Minimum bending radius permanent (multi core)
7.5 x D
Resistenza minima allo schiacciamento / 10cm
1000
N
System Circuit Integrity is dependent on installation method.
Conduttore
Bare copper, solid, 0.8 mm diameter, VDE 0815
Isolamento
Fire-resistant, cross-linked, high-performance Keram special compound, EN 50290-2-36
Colori delle anime
VDE 0815
Shielding
Al-laminated tape with copper drain wire Ø 0.8 mm
Materiale della guaina esterna
Flame retardant polyolefin compound VDE 0819-107, EN 50290-2-27 and VDE 0250-214 "HM 2"