J-H(St)H...Bd fire alarm

Fire alarm cable, max. 300V
halogen-free, with improved fire characteristics,
VDE 0815

1 Conductor: solid
2 Insulatio: halogen-free polymer compound
3 Separator: plastic tape
4 Drain wire: tinned copper
5 Shielding: Al-laminated plastic foil
6 Sheath: FRNC/LSZH

07_Circuit- 04_Propagation 05_Spread 06_Density 08_System- 03_LS0H

Varianti di prodotto e stock

Articolo n. Stock ProdottoColore della guaina esternaNumero di coreDiametro esterno della guaina [mm]Tasso di CU [kg/km]Weight [kg/km]Fire load [kWh/m]Unità di imballaggioGTIN / EAN
157892
J-H(St)H...Bd fire alarm 2x2x0,8 mmrosso26.525590.16al metro40393910207637
157893
J-H(St)H...Bd fire alarm 4x2x0,8 mmrosso28.5451110.29al metro40393910207620
157894
J-H(St)H...Bd fire alarm 6x2x0,8 mmrosso210.5651320.35al metro40393910207613
157895
J-H(St)H...Bd fire alarm 10x2x0,8 mmrosso2131062160.55al metro40393910207606
1172017
J-H(St)H...Bd fire alarm 20x2x0,8 mmrosso215.52065081.21al metro40393910107104
1172018
J-H(St)H...Bd fire alarm 30x2x0,8 mmrosso216.33075991.36al metro40393910107098
1172019
J-H(St)H...Bd fire alarm 40x2x0,8 mmrosso216.54077871.67al metro40393910107081
1172021
J-H(St)H...Bd fire alarm 80x2x0,8 mmrosso231.580914763.18al metro40393910107074
1172022
J-H(St)H...Bd fire alarm 100x2x0,8 mmrosso238101018054.07al metro40393910107067

Specifiche tecniche

Installation cable with electrostatic shield for areas vulnerable to fire and with high concentration of people and property value. For ICT systems for lossless data and signal transmission. Suitable for laying in dry and humid rooms, on-wall and in-wall, also for outdoor use.
No underground laying. Not to be used for high-voltage transmission.
Permitted operating temperature at conductor of +70°C.
operating capacity, 1km @ 800Hz 120
Test voltage 50Hz, core/core 800
peak voltage 300
Capacitive coupling 0,8 mm, 100m @ 800Hz 200
Capacitive coupling 0,6 mm, 100m @ 800Hz 300
resistenza massima del loop 0,8 mm 73.2
resistenza massima del loop 0,6 mm 130
Minimum insulation resistance 100
Test voltage 50Hz, core/screen 800
Integrità dell'isolamento No
Integrità del circuito No
Installation temperature -5 °C - +50 °C
Operating temperature -30 °C - +70 °C
Curvatura minima durante l'installazione (multicore) 7.5 x D
Minimum bending radius permanent (multi core) 2.5 x D
Additional dimensions available on request.
Conduttore Bare copper, solid, 0.6 or 0.8 mm diameter
Isolamento Halogen-free polymer compound, EN 50290-2-26
Colori delle anime VDE 0815
Shielding Al-laminated plastic foil with drain wire, copper tinned
Materiale della guaina esterna Halogen-free polymer compound, EN 50290-2-27
Stranding Cores twisted to star-quads and quads to units
Densità del fumo IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero alogeni nessun gas corrosivo IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Propagazione della fiamma AREI-RGIE Section 4.3.3 F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24, EN 60332-3-24, AREI-RGIE Section 4.3.3 F2

Documentazione