Safety cable, 0.6/1kV, armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core)
12 x D
Curvatura minima durante l'installazione (anima singola)
15 x D
Minimum bending radius permanent (single core)
15 x D
Curvatura minima durante l'installazione (multicore)
12 x D
Integrità dell'isolamento
FE 180
Integrità del circuito
E30
Installation temperature
-5 °C - +50 °C
Operating temperature
-45 °C - +90 °C
Tensione di prova a 50Hz
3500
Nominal voltage
0.6/1kV
* System Circuit Integrity is dependent on installation method
Conduttore
Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Isolamento
Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Colori delle anime
CENELEC HD 308 S2
Riempitrice
HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Guaina interna
Compound, HD 604 S1 part 5 H(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 ""HM 4"", flame-retardant)
Armatura (protezione per roditori)
Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Materiale della guaina esterna
Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)