Armoured Standard Fire Safety Cable
Fire alarm cable, 300/500V, with steel wire braiding
halogen-free, with improved fire characteristics,
with reference to BS 7629-1
1 Conductor: solid or stranded
2 Insulation: fire resistant special compound
3 Drain wire: tinned copper
4 Inner covering: glass fibre tape
5 Shielding: Alu-laminated tape
6 Inner sheath: Polyolefin compound
7 Armouring: galvanised steel wire band
8 Sheath: FRNC/LSZH






Varianti di prodotto e stock
Scaricare
Articolo n. | Stock | Prodotto | Colore della guaina esterna | Diametro mm² | Diametro esterno della guaina [mm] | Tasso di CU [kg/km] | Weight [kg/km] | Fire load [kWh/m] | GTIN / EAN |
---|---|---|---|---|---|---|---|---|---|
194031 | Armoured Standard Fire Safety Cable | rosso | 1.5 | 11.5 | 48 | 184 | 0.40 | 40393910064834 |
Specifiche tecniche
Armoured cable for fire alarm systems and emergency lighting for permament installation in buildings.
Permitted operating temperature at conductor of +90˚C.
Permitted operating temperature at conductor of +90˚C.
Tensione di prova a 50Hz | 2000 |
---|---|
Nominal voltage | 300/500V |
Curvatura minima durante l'installazione (multicore) | 6 x D |
---|---|
Minimum bending radius permanent (multi core) | 6 x D |
Additional dimensions available on request. |
Conduttore | Bare copper, solid or stranded in accordance with IEC 60228 and EN 60228 |
---|---|
Isolamento | Special compound, BS EN 50363-5 |
Colori delle anime | 2 cores + earth: blue, brown; 3 cores + earth: brown, black, grey, 4 cores + earth: blue, brown, black, grey |
Shielding | Al-laminated tape and tinned copper drain wire, IEC 60228 class 1or 2, EN 60228 |
Guaina interna | Polyolefin compound |
Armatura (protezione per roditori) | Stahldrahtgeflecht mit ca. 70% Überdeckung |
Materiale della guaina esterna | Polyolefin compound, BS 7655-6.1, LTS3 |
Installation temperature | -5 °C - +50 °C |
---|---|
Operating temperature | -15 °C - +90 °C |
Integrità del circuito | IEC 60331-11/-21 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-2 (120 minutes), BS EN 50200 Annex E, VDE 0482-200 (PH120), AREI-RGIE Section 4.3.3 FR1, BS EN 50200 (PH120) |
---|---|
Densità del fumo | IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD |
Zero alogeni nessun gas corrosivo | IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA |
Propagazione della fiamma | AREI-RGIE Section 4.3.3 F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2 |
Flame spread | IEC 60332-3-22/-24, EN 60332-3-22/-24, VDE 0482-332-3-22/-24, AREI-RGIE Section 4.3.3 F2 |