Safety cable, 0.6/1kV, armoured with rodent protection, Keram
halogen-free, with improved fire characteristics,
with reference to SEV TP 20B/3C and CENELEC HD 604 S1 part 5.H
Safety cables are installed in all areas that require special protection of people and equipment against fire and fire damages and where strict security requirements must be fulfilled.
Suitable for indoor applications. For outdoor applications, protection must be provided against exposure to direct sunlight. The cable should only be laid directly in earth or water if a protective conduit is used.
Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core)
12 x D
Minimum bending during installation (single core)
15 x D
Minimum bending radius permanent (single core)
15 x D
Minimum bending during installation (multi core)
12 x D
Circuit integrity
FE 180
System circuit integrity
E30
Installation temperature
-5 °C - +50 °C
Operating temperature
-45 °C - +90 °C
Test voltage at 50Hz
3500
Nominal voltage
0.6/1kV
* System Circuit Integrity is dependent on installation method
Conductor
Bare copper, solid or stranded, IEC 60228 and EN 60228 (≥16 mm2: VDE 0295)
Insulation
Special compound, HD 604 S1 part 5 H(≥16 mm2: double-layer insulation, special compound, VDE 0266 "HXI1")
Core colours
CENELEC HD 308 S2
Filler
HD 604 S1 part 5 H(≥16 mm2: halogen-free polyolefin compound)
Inner sheath
Compound, HD 604 S1 part 5 H(≥16 mm2: Polyolefin compound, VDE 0276-604, CENELEC HD 604 S1 ""HM 4"", flame-retardant)
Armouring (rodent protection)
Single-core cable with copper tape (CLCU) and multicore cable with galvanised steel tape (CL)
Outer sheath material
Compound, HD 604 S1 part 5 H(16 mm2: in accordance with CENELEC HD 308 S2 and VDE 0293)