Enhanced Fire Safety Cable solid

Fire alarm cable, 300/500V
halogen-free, with improved fire characteristics,
BS 7629-1 and BS 5839-1 Enhanced

1 Conductor: solid
2 Insulation: Mica fire resistant tape
3 Silicon rubber
4 Drain wire: tinned copper
5 Shielding: Aluminium/polyester tape
6 Sheath: FRNC/LSZH

05_Spread 04_Propagation 08_System- 03_LS0H 07_Circuit 06_Density

Product variants & stock

Article No. Stock ProductOuter sheath colourDiameter mm²Outer sheath diameter [mm]CU rate [kg/km]Resistance [Ω/km]Voltage drop [Ω mV/A/m]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
18836810ZL
Enhanced Fire Safety Cable 2 x 1.5red1.58.64312.1291150.19500 m drum40393910095913
18836810ZM
Enhanced Fire Safety Cable 2 x 1.5red1.58.64312.1291150.19200 m drum40393910095906
18836810ZN
Enhanced Fire Safety Cable 2 x 1.5red1.58.64312.1291150.19100 m drum40393910095890
18836910ZL
Enhanced Fire Safety Cable 2 x 1.5white1.58.64312.1291150.19500 m drum40393910095852
18836910ZM
Enhanced Fire Safety Cable 2 x 1.5white1.58.64312.1291150.19200 m drum40393910095845
18836910ZN
Enhanced Fire Safety Cable 2 x 1.5white1.58.64312.1291150.19100 m drum40393910095838
18837010ZL
Enhanced Fire Safety Cable 2 x 2.5red2.59.9727.41181600.26500 m drum40393910095791
18837010ZM
Enhanced Fire Safety Cable 2 x 2.5red2.59.9727.41181600.26200 m drum40393910095784
18837010ZN
Enhanced Fire Safety Cable 2 x 2.5red2.59.9727.41181600.26100 m drum40393910095777
18837110ZL
Enhanced Fire Safety Cable 2 x 2.5white2.59.9727.41181600.26500 m drum40393910095739
18837110ZM
Enhanced Fire Safety Cable 2 x 2.5white2.59.9727.41181600.26200 m drum40393910095722
18837110ZN
Enhanced Fire Safety Cable 2 x 2.5white2.59.9727.41181600.26100 m drum40393910095715
19167910ZL
Enhanced Fire Safety Cable 4 x 1.5red1.510.17212.1291800.28500 m drum40393910095005
19167910ZM
Enhanced Fire Safety Cable 4 x 1.5red1.510.17212.1291800.28200 m drum40393910094992
19167910ZN
Enhanced Fire Safety Cable 4 x 1.5red1.510.17212.1291800.28100 m drum40393910094985
19632910ZL
Enhanced Fire Safety Cable 4 x 1.5white1.510.17212.1291800.28500 m drum40393910094046
19632910ZM
Enhanced Fire Safety Cable 4 x 1.5white1.510.17212.1291800.28200 m drum40393910094039
19632910ZN
Enhanced Fire Safety Cable 4 x 1.5white1.510.17212.1291800.28100 m drum40393910094022

Technical specifications

Cable for fire alarm systems and emergency lighting for permanent installation in buildings. Permitted operating temperature at conductor of +90˚C.
Minimum bending radius permanent (multi core) 6 x D
Minimum bending during installation (multi core) 6 x D
Circuit integrity PH 120
Installation temperature -5 °C - +50 °C
Operating temperature -40 °C - +90 °C
Test voltage at 50Hz 2000
Nominal voltage 300/500V
Typical applications are:
BS 5839-1 for enhanced fire resistant cables in fire detection and fire alarm systems for building
BS 5839-8 for voice alarm systems
BS 5839-9 for emergency voice communication systems
BS 5266-1 for emergency ligthing of premises
BS 8519 for fire-resistant control cable systems for life safety and fire-fighting application - Category 2 and 3
Additional dimensions available on request.
Conductor Plain annealed copper wire, solid class 1, EN 60228
Insulation Mica/Glass fire resistant tape. Fire resistant silicon rubber type EI2 to BS EN 50363-1
Core colours HD 308 S2, BS 7629-1
Shielding Aluminium/polyester tape and uninsulated tinned copper drain wire; IEC 60228, EN 60228
Outer sheath material Polyolefin compound, BS 7655-6.1, LTS3
Circuit integrity IEC 60331 (180 minutes), VDE 0472-814 (FE180), BS 6387 C/W/Z, IEC 60331-2 (120 minutes), VDE 0482-200 (PH120), BS EN 50200 (PH120)
Smoke density IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Zero halogen no corrosive gases IEC 60754-1, EN 60754-1, VDE 0482-754-1
Flame propagation IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
LPCB Certificate LPCB Certificate Number: 172h, Issue: 02

Documentation