CU 7002 4P GG-PE

Data cable, S/FTP, Category 7, AWG23, Euroclass Fca
1000 MHz

1 Inner conductor: AWG23 Bare copper wire
2 PE insulated conductor: 1.4 mm Ø
3 Screen (pair): Alu PETP foil
4 Overall screen: Tinned braided copper
5 Sheath: FRNC/LS0H orange RAL 2003
6 Rodent protection: with glass rovings
7 Ripcord
8 Outer sheath: PE black

01_RoHS 04_Propagation- 05_Spread- 02_PoEp_rt 10_Schielded_EN 06_Density 08_System- 03_LS0H CPR_Fca

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
19192300FZ
CU 7002 4PFca4 x 2 x 0.57 (AWG23)11.431.1129.50.648by the metre40393910029420

Technical specifications

Applicable for outdoor installation due to rodent protection and PE outer cable sheath with higher UV resistance.
Robust cable design with a high mechanical stability.
Electrically and mechanically superior quality Cat.7 data cable - exceeds the requirements of ISO/IEC 11801, IEC 61156-5, EN 50173-1 and EN 50288-4-1.
Excellent shielding effect due to individually screened pairs and overall copper braid.
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801.
Minimum bending radius (during installation) 92 mm
Tensile strength (4P) 150 N
Minimum number of impacts 20
Minimal crush resistance / 10cm 2000 N
AWG 23
Solid / Flex Solid wire
Minimum bending radius (permanently installed) 46 mm
Data cable for structured premises and outdoor cabling.
With rodent protection and increased UV protection (due to PE outer sheath).
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class F applications (600 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+ / 4PPoE up to 100W.
The cables are designed for occasional contact with water, but are not suitable for permanent installation or total immersion in water. The cable jacket is designed to resist water, but should be avoided coming into direct contact with water for a long time.
To prevent water from entering, the cable jacket must remain intact. It is necessary to prevent water from entering the ends of the cable. This also requires a suitable connection system.
When laying directly underground, care must be taken to ensure that no point mechanical loads occur, as the mechanical structure is unsuitable for laying in a gravel bed, for example.
Laying in protective shells made of concrete (cable duct blocks) or steel or in plastic pipes is recommended. Where the cable comes into direct contact with the ground, embedding in a sand bed is recommended.
Category Cat.7
GBit/s Up to 10 Gbit/s
Loop resistance at 20 °C 140 Ω/km
Operating capacity 42 pF/m
Impedance at 100 MHz, ±5Ω 100 Ω
NVP % 81
Delay skew 12 ns/100 m
Shielding shielded
Near end unbalance attenuation LCL at 1-600 MHz 40 dB
Coupling attenuation 85 dB
Segregation class d
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Wire colour white/blue, white/orange, white/green, white/brown, according to IEC 60189 and IEC 60708
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Field of application Outdoor
Reaction to fire EN 13501-6
Euroclass Fca
Smoke density IEC 61034-1/-2, EN 61034-1/-2, VDE 0482-1034-1/-2, AREI-RGIE Section 4.3.3 SD
Zero halogen no corrosive gases IEC 60754-1/-2, EN 60754-1/-2, VDE 0482-754-1/-2, AREI-RGIE Section 4.3.3 SA
Cables standard ISO/IEC 61156-5, EN 50288-4-1
Cat./Class Cat.7 / Class F
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH-GG-PE
Outer sheath colour black

Documentation