CU 662 4P

Data cable, U/UTP, Category 6, AWG23, Euroclass Cca
300 MHz

1 Inner conductor: AWG23/0,55 mm Bare Copper wire
2 PE insulated conductor: 0.98 mm Ø
3 Pair seperator
4 Outer sheath: FRNC/LSoH orange RAL 2003

06_Density 10_Schielded-_EN 09_Oil- 05_Spread- CPR_Dca 08_System- CPR_Eca 03_LS0H 01_RoHS 04_Propagation CPR_Cca 02_PoE CPR_Fca

Product variants & stock

Article No. Stock ProductReaction to fireDimensions n x p x [mm (AWG)]Outer sheath colourOuter sheath dimensions [mm]CU rate [kg/km]Weight [kg/km]Fire load [kWh/m]Packing unitGTIN / EAN
19463100CL
CU 662 4PCca-s1a,d1,a14 x 2 x 0.55 (AWG23)orange6.319.5460.19500 m drum40393910021271
19463100CP
CU 662 4PCca-s1a,d1,a14 x 2 x 0.55 (AWG23)orange6.319.5490.19305 m PullQuick box40393910021264

Technical specifications

Electrically and mechanically advanced quality Cat.6 data cable - fulfils the requirements of ISO/IEC 11801-1, IEC 61156-5, EN 50173-1 and EN 50288-6-1.
Robust cable design with reliable electrical performance thanks to stabilising element.
Very good NEXT reserve due to cable construction with a pair separator (cross).
Compatible with all current connecting hardware in accordance with EN 50173 and ISO/IEC 11801-1.
Minimum bending radius (during installation) 45 mm
Tensile strength (4P) 91 N
Minimum number of impacts 10
Minimal crush resistance / 10cm 1000 N
AWG 23
Solid / Flex Solid wire
Minimum bending radius (permanently installed) 22.5 mm
Data cable for structured premesis cabling.
For the transmission of digital and analogue voice, video and data signals.
Suitable for all ICT network applications up to class E applications (250 MHz) in accordance with EN 50173-1 and ISO/IEC 11801.
Applicable for Power over Ethernet (PoE) / PoE+.
Category Cat.6
GBit/s Up to 1 Gbit/s
Loop resistance at 20 °C 155 Ω/km
Operating capacity 50 pF/m
Impedance at 100 MHz, ±5Ω 100 Ω
NVP % 67
Delay skew 20 ns/100 m
Shielding unshielded
TCL 50 dB
Segregation class b
Installation temperature 0 °C - +50 °C
Operating temperature -20 °C - +60 °C
Imprint DATWYLER «cable type» «additional text» «batch number» «meter marks»
Field of application Indoor
Reaction to fire EN 13501-6
Euroclass Cca
Smoke density AREI-RGIE Art.104-SD - applies to FRNC/LS0H, EN 61034-1/-2, IEC 61034-1/-2, VDE 0482-1034-1/-2
Zero halogen no corrosive gases AREI-RGIE Art.104-SA, EN 60754-1/-2, IEC 60754-1/-2, VDE 0482-754-1/-2
Flame propagation AREI-RGIE Art.104-F1, EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2
Cables standard ISO/IEC 61156-5, EN 50288-6-1
Cat./Class Cat.6 / Class E
PoE IEEE 802.3bt Type 4 (100W)
Outer sheath material FRNC/LSZH

Documentation